Plan Review Notes For Permit 03101403 |
Permit Number |
03101403 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-30 00:00:00 | 1) LIFE SAFETY ANALYSIS BOX MAKES | | SEVERAL REFERENCES TO THE BUILDING | | BEING FIRE SPRINKLER PROTECTED. NO | | FIRE SPRINKLER DRAWINGS HAVE BEEN | | PROVIDED. THE ANALYSIS BOX ALSO | | INDICATES EXCEPTIONS TO THE CODE BY | | USING THE FIRE SPRINKLER EXCEPTIONS. | | | | 2) EXITS DO NOT APPEAR TO MEET ONE | | HALF THE DIAGONAL RULE IF YOU DO NOT | | SPRINKLER PROTECT THE BUILDING. PLEASE | | EXPLAIN. SPRINKLER PROTECTION AFFORDS | | THE ONE THIRD THE DISTANCE RULE. | | | | 3) PLEASE PROVIDE DETAILS ON FOAM | | COLUMNS. | | | | 4) BUILDING ADDRESS REQUIRED ON | | PROPER ELEVATION. | | | | 5) IT APPEARS MECHANICAL EQUIPMENT IS | | PRESENT WITHIN THE NORTHEAST STAIRWELL. | | PLEASE ADVISE IF THIS EQUIPMENT MEETS | | THE FBC OR THE FFPC FOR PERMITTED | | EQUIPMENT. | | | | 6) TACTILE SIGNAGE REQUIRED AT STAIRWELL | | DOORS. | | | | 7) SEPARATE PLANS AND PERMITS REQUIRED | | FOR FIRE ALARM SYSTEM. | | | | 8) SHAFTWAYS ARE TO BE MARKED. | | | | 9) SINGLE OR MULTIPLE TENANTS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|