Plan Review Notes
Plan Review Notes For Permit 03101403
Permit Number 03101403
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-10-30 00:00:001) LIFE SAFETY ANALYSIS BOX MAKES
 SEVERAL REFERENCES TO THE BUILDING
 BEING FIRE SPRINKLER PROTECTED. NO
 FIRE SPRINKLER DRAWINGS HAVE BEEN
 PROVIDED. THE ANALYSIS BOX ALSO
 INDICATES EXCEPTIONS TO THE CODE BY
 USING THE FIRE SPRINKLER EXCEPTIONS.
  
 2) EXITS DO NOT APPEAR TO MEET ONE
 HALF THE DIAGONAL RULE IF YOU DO NOT
 SPRINKLER PROTECT THE BUILDING. PLEASE
 EXPLAIN. SPRINKLER PROTECTION AFFORDS
 THE ONE THIRD THE DISTANCE RULE.
  
 3) PLEASE PROVIDE DETAILS ON FOAM
 COLUMNS.
  
 4) BUILDING ADDRESS REQUIRED ON
 PROPER ELEVATION.
  
 5) IT APPEARS MECHANICAL EQUIPMENT IS
 PRESENT WITHIN THE NORTHEAST STAIRWELL.
 PLEASE ADVISE IF THIS EQUIPMENT MEETS
 THE FBC OR THE FFPC FOR PERMITTED
 EQUIPMENT.
  
 6) TACTILE SIGNAGE REQUIRED AT STAIRWELL
 DOORS.
  
 7) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 8) SHAFTWAYS ARE TO BE MARKED.
  
 9) SINGLE OR MULTIPLE TENANTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910