2003-11-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03101403
 ADD: 310 EVERNIA
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) SHEET A-1 INDICATES THAT THIS BUILD-
 ING IS TO BE FIRE SPRINKLERED, BUT NO
 PLANS WERE SUBMITTED?
  
 2) DUCTWORK IN STAIRWELL: 1006.1.3.1.
 PENETRATIONS INTO AND OPENINGS THROUGH A
 STAIRWAY ENCLOSURE ASSEMBLY ARE PROHIBIT
 ED EXCEPT FOR REQUIRED EXIT DOORS, DUCT-
 WORK AND EQUIPMENT NECESSARY FOR INDEPEN
 DENT STAIR PRESSURIZATION, SPRINKLER
 PIPING, STANDPIPES AND ELECTRICAL CON-
 DUIT SERVING THE STAIRWAY AND TERMINAT-
 ING AT A STEEL BOX NOT EXCEEDING 16 SQ
 INCHES.
  
 3) FOAM COLUMNS AND PILASTERS: 803.4
 FOAM PLASTIC TRIM SHALL NOT BE FOR TRIM,
 SEE EXCEPTIONS! PROVIDE ADDITIONAL INFOR
 MATION.
  
 4)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 STAIRS RISE & RUN GUARDRAILS, HANDRAILS
 AND EXTENSIONS.
  
 5)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 AC-1 INDICATES A SKYLIGHT IS THIS EXIST-
 ING OR IS IT NEW?
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORT:
 A) FRENCH DOORS/ STORM SHUTTERS
  
 7) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 8)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE
 MECHANICAL EQUIPMENT, APPLIANCES AND SUP
 PORTS THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026