2003-10-24 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CHANGES TO
 PLAN FOR CODE COMPLIANCE,AND RESUBMIT
 FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY ARCH/ OR
 ENGINEER ARE REQ`D PER 61G15-23.002 FOR
 ENGINEER AND 61G1-16.004 FOR ARCH.
 SHALL HAVE A TITLE BLOCK.ALSO A WET
 SIGNATURE.
  
 3} PLEASE NOTE THAT THE DRYER LISTED ON
 THE PANEL SCHEDULE IS SHOWN AT 20 AMPS.
 SEE 220.18.
  
 4} PLEASE DO LOAD CALCULATIONS PER
 220.30,220.31 OR SHOW A GENERAL LOAD
 CALC PER ARTICLE 220.
  
 5} PLEASE NOTE THE GEC MUST COMPLY WITH
 250.66,INDICATE ON THE RISER DIAGRAM.
  
 6} THE PANEL SCHEDULE INDICATES NEW
 SMALL APPLIANCE CIRCUITS,BUT NO WORK TO
 THE KITCHEN IS INDICATED IN THE SCOPE
 OF WORK FOR THIS PERMIT.THE LAST
 ELECTRICAL PERMIT ISSUED BESIDES LOW
 VOLTAGE WAS IN 1997 AND FOR A PANEL
 RELOCATION.IF THE KITCHEN IS TO BE
 REWIRED PLEASE INDICATE SAME ON THE
 PERMIT APPLICATION AND INCLUDE IN THE
 VALUE OF THE JOB.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECRICAL PLAN REVIEW
 561/805-6718