2003-12-06 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 A) THE FOLLOWING INFORMATION STILL RE-
 QUIRED FOR GAS PERMIT.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. SEE PLANS OF SECTIONS OF
 PIPE WITH NO MEASURMENTS.
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). NOT SHOWN
 3. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. RESPONSE NOTED,
 BUT SECTION 303.3 STATES, "FUEL-FIRED
 APPLIANCES SHALL NOT BE LOCATED IN, OR
 OBTAIN COMBUSTION AIR FROM, ANY OF THE
 FOLLOWING ROOMS OR SPACES:
 1. SLEEPING ROOMS. 2. BATHROOMS. 3. TOI-
 LET ROOMS. 4. STORAGE CLOSETS ECT.
 4) IF THE PRESSURE FOR THIS SYSTEM IS
 2 LBS, THEN REGULATORS SHALL BE REQUIRED
 AT EACH APPLIANCE. 1" PIPE WILL SUPPLY
 UP TO 260,000 BTU'S UP TO 60' WITH .5PSI
 SO 2 LB IS NOT NEEDED. PLEASE CLAIRFY.
  