Date |
Text |
2003-12-06 00:00:00 | DENIED |
| REFERENCE: FBC-2001 FUEL GAS |
| |
| A) THE FOLLOWING INFORMATION STILL RE- |
| QUIRED FOR GAS PERMIT. |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. SEE PLANS OF SECTIONS OF |
| PIPE WITH NO MEASURMENTS. |
| 2. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). NOT SHOWN |
| 3. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| GAS CODE SECTION 304. RESPONSE NOTED, |
| BUT SECTION 303.3 STATES, "FUEL-FIRED |
| APPLIANCES SHALL NOT BE LOCATED IN, OR |
| OBTAIN COMBUSTION AIR FROM, ANY OF THE |
| FOLLOWING ROOMS OR SPACES: |
| 1. SLEEPING ROOMS. 2. BATHROOMS. 3. TOI- |
| LET ROOMS. 4. STORAGE CLOSETS ECT. |
| 4) IF THE PRESSURE FOR THIS SYSTEM IS |
| 2 LBS, THEN REGULATORS SHALL BE REQUIRED |
| AT EACH APPLIANCE. 1" PIPE WILL SUPPLY |
| UP TO 260,000 BTU'S UP TO 60' WITH .5PSI |
| SO 2 LB IS NOT NEEDED. PLEASE CLAIRFY. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |