2003-10-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. KITCHEN AND BAR SINK
 ARE NOT VENTED. SUBMIT SANT. RISER DIA-
 GRAM IN AN ISOMETRIC FORM. SHOW VENTS.
 WASH MACHINE REQUIRES A C/O AT 4' ABOVE
 THE FLOOR. 708.10 - 901.2.1
 2) SEPARATE PERMIT REQUIRED FOR GAS.
 THE FOLLOWING INFORMATION IS REQUIRED AT
 APPLICATION FOR GAS PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. FOR WATER HEATER
 AND DRYER.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 3) SEE ATTACHED SHEET CONCERNING DESIGN
 PROFESSIONALS. TITLE BLOCK REQUIRED WITH
 INFORMATION STATED PER 61G1-16.004
  
 REVIEW BY KEN STEVENS