Date |
Text |
2003-10-25 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| |
| 1) SANITARY RISER DIAGRAM DOES NOT MEET |
| CODE REQUIREMENTS. KITCHEN AND BAR SINK |
| ARE NOT VENTED. SUBMIT SANT. RISER DIA- |
| GRAM IN AN ISOMETRIC FORM. SHOW VENTS. |
| WASH MACHINE REQUIRES A C/O AT 4' ABOVE |
| THE FLOOR. 708.10 - 901.2.1 |
| 2) SEPARATE PERMIT REQUIRED FOR GAS. |
| THE FOLLOWING INFORMATION IS REQUIRED AT |
| APPLICATION FOR GAS PERMIT. |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF USED. |
| C. TYPE OF GAS, (LP OR NATURAL) |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34). |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). |
| F. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| GAS CODE SECTION 304. FOR WATER HEATER |
| AND DRYER. |
| G. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| 3) SEE ATTACHED SHEET CONCERNING DESIGN |
| PROFESSIONALS. TITLE BLOCK REQUIRED WITH |
| INFORMATION STATED PER 61G1-16.004 |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |