Plan Review Notes For Permit 03101014 |
Permit Number |
03101014 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-21 00:00:00 | PROVISO: | | 1.DUCT SMOKE DETECTOR SHALL BE | | INSTALLED IN THE SUPPLY AIR DUCT AS PER | | 2001 FBC(M) 606.2.1. | | | | 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | IN NORMALLY OCCUPIED AREAS AS PER NFPA | | 90A 4-4.4.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|