Plan Review Notes
Plan Review Notes For Permit 03101014
Permit Number 03101014
Review Stop M
Sequence Number 1
Notes
Date Text
2003-10-21 00:00:00PROVISO:
 1.DUCT SMOKE DETECTOR SHALL BE
 INSTALLED IN THE SUPPLY AIR DUCT AS PER
 2001 FBC(M) 606.2.1.
  
 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS AS PER NFPA
 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.