Plan Review Notes For Permit 03101002 |
Permit Number |
03101002 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-27 00:00:00 | *************** UNSAT ************* | | | | 1)NOTE: PLEASE SUBMIT AIC RATING FOR | | ALL SERVICE EQUIPMENT. MAINS/PANELS/BRKR | | -S ARE ALL TO BE RATED FOR THE THE | | AVIALABLE FAULT CURRENT. 110.9/ 215.5 | | | | 2)NOTE: PLEASE SEE MISSING RECEPT IN | | WAHT APPEARS TO BE DINING RM? 2' OF WALL | | SPACE. 210.52 | | | | 3)NOTE: PLEASE SEE MISSING RECEPT FOR | | KITCHEN COUNTERSPACE PER 210.52C1 | | | | 4)NOTE : PLEASE SEE OCP SHOWN FOR 5KW | | AHU, SHOWS 2P60? PLEASE CORRELATE. | | PER 424.3B | | | | 5)NOTE: PLEASE SEE PLACEMENT OF RECEPT | | IN MASTER BATH. TO BE W/IN 3' OF SINK. | | 210.52D | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR] | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL.. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|