Date |
Text |
2003-11-17 00:00:00 | UNSAT |
| |
| 1) THE LETTER FROM THE ARCHITECT |
| ADDRESSING THE TRUSSES DOES NOT HAVE AN |
| ORIGINAL WET SIGNATURE. THERE IS NOTHING |
| ON THE PLANS INDICATING THE MODEL TO |
| WHICH THE LETTER REFERS. |
| |
| 2) SPECIFY ON THE PLANS THAT THE WWF IN |
| THE SLAB WILL BE SUPPORTED AT 3'OC AS |
| REQUIRED BY FBC 1909.3. |
| |
| 3) THE STAIRS FROM THE LOFT TO THE BED |
| ROOMS DO NOT COMPLY WITH FBC 1007.3. THE |
| SUM OF TWO RISERS AND A TREAD EXCLUSIVE |
| OF THE NOSING SHALL BE NO LESS THAN 24" |
| NOR MORE THAN 25". |
| |
| 4) HANDRAILS 34"- 38" HIGH ARE REQUIRED |
| FOR STAIRWAYS WITH FOUR OR MORE RISERS |
| PER FBC 1007.5. HANDRAILS MUST PROVIDE |
| GRASPABILITY AS REQUIRED BY FBC 1007.5.3 |
| GUARDRAILS FOR DWELLING SHALL BE A MIN. |
| OF 36" HIGH PER FBC 1026.5. |
| |
| 5) THE 120 SQ.IN. VENT IN THE GARAGE CAN |
| NOT BE LOCATED IN THE WALL ON THE ZERO |
| LOT LINE. NO OPENINGS ARE ALLOWED IN |
| THIS WALL PER FBC TABLE 600. |
| |
| 6) ON THE FRAMING PLAN ON A7 A LINTEL |
| (L1) IS INDICATED AT THE SHOWER IN THE |
| MASTER BEDROOM. NO OPENING IS SHOWN ON |
| THE FLOOR PLAN AT THIS LOCATION. PLEASE |
| CLARIFY. |
| |
| 7) PRODUCT APPROVALS SUBMITTED WITH |
| APPLICATIONS AFTER OCTOBER 1, 2003 ARE |
| REQUIRED TO COMPLY WITH THE STATE OF |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION SEE THE STATE WEBSITE AT WWW |
| FLORIDABUILDING.ORG. PRODUCTS WITH STATE |
| APPROVAL ARE REQUIRED TO BE SUBMITTED |
| WITH A COVER SHEET WHICH LISTS THE |
| PRODUCT IDENTITY NUMBER FROM THE STATE. |
| IF THE PRODUCT DOES NOT HAVE A STATEWIDE |
| PRODUCT APPROVAL, SUBMIT AN APPLICATION |
| FOR LOCAL PRODUCT APPROVAL PER RULE |
| 9B-72. SEE ATTACHMENT. |
| |
| 8) FBC 1606.1.4 REQUIRES EXTERIOR |
| GLAZING PROTECTION IN WINDBORNE DEBRIS |
| REGIONS. PROVIDE (2) PRODUCT APPROVALS, |
| KEY PLANS AND INSTALLATION SCHEDULES |
| INDICATING THE SPECIFIC TYPES OF ANCHORS |
| TO BE USED FOR STORM PANELS. |
| |
| 9)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR THE SINGLE OUTSWING FRONT |
| DOOR. THE ONE THAT WAS SUBMITTED IS FOR |
| DOUBLE OUTSWING DOORS ONLY. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |