Plan Review Notes For Permit 03100990
Permit Number 03100990
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-23 00:00:00************** UNSAT **********
  
 1)NOTE: PLEASE SUBMIT PANEL SCHEDULE
 SHOWING ALL MIN REQ'D CIRCUITS, OCP AND
 WIRE SIZE.
 LIST ALL DEDICATED CIRCUITS ETC.
 KITCHEN/BATHS/ARC FAULT/WASHER/ETC ETC
 220, 210, 215.5 ,210.12,210.52,210.11
 SHOW LOAD CALC AND EXISTING SERVICE SIZE
  
 2)NOTE: PLEASE SEE 210.52E FOR FRONT
 AND REAR RECEPTS.
  
 3)NOTE: PLEASE SEE SOME RECEPTS MISSING
 IN WHAT APPEARS TO BE KITCHEN.210.52
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  