Plan Review Notes
Plan Review Notes For Permit 03100751
Permit Number 03100751
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-22 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 AND
 INCLUDE ALL LICENSE INFORMATION ON TITLE
 BLOCK. PER FS 471
  
 2)NOTE: PLEASE SEE THAT WE ARE NOW UNDER
 THE 2002 NEC AND REQUIREMENTS FOR 210.12
 HAVE CHANGED. PLANS MENTIONS RECEPTS.
 THIS IS NO LONGER THE CASE.
  
 3)NOTE: PLEASE SEE RISER, SHOWS A METER/
 MAIN COMBO AND STILL SHOWS SUB PANEL "A"
 AS MCB. THIS IS PERMITTED, HOWEVER IF
 SHOWN, THEN A MCB WILL BE REQ'D TO BE
 INSTALLED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]