2003-11-04 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| |
| 1) THESE SPACES WERE RESIDENTIAL OCCU- |
| PANCIES. AS A CHANGE OF OCCUPANCY FROM |
| RESIDENTIAL TO COMMERCIAL, SECTION |
| 3402.2.2.1 THE BUILDING, ELECTRICAL, GAS |
| MECHANICAL AND PLUMBING SYSTEMS SHALL BE |
| MADE TO COMFORM TO THE INTENT OF THE |
| TECHNICAL CODES AS REQUIRED BY THE BLDG. |
| OFFICIAL. |
| 2) IF BATHING FACILITIES ARE PROVIDED ON |
| A SITE THEN EACH SUCH PUBLIC OR COMMON |
| USE BATHING FACILITY SHALL COMPLY WITH |
| 11-4.23.SECTION 11-4.1.2(6) |
| SUBMIT DETAIL FOR FOR BOTH THE TOILET |
| ROOM AND THE BATHING SHOWING COMPLIANCE |
| WITH SECTIONS 11-4.22, & 11-4.23 AND |
| ALL SUBSECTIONS. SHOW COMPLIANCE WITH |
| 11-4.16, 11-4.19, & 11-4.20 AND ALL SUB- |
| SECTIONS. SEE FIGURES 28, 29, 32, 33, & |
| 34. |
| 3) BREAKROOM SINK SHALL COMPLY WITH |
| SECTION 11-4.24 AND ALL SUBSECTIONS. |
| PROVIDE DETAILS. |
| 4) BATHTUB THAT WILL BE COVERED SHALL |
| HAVE THE WASTE AND OVERFLOW SEALED TO |
| KEEP SEWER GASSES FROM ESCAPING. |
| 5) ALL CAPPED WATER AND SANITARY LINES |
| SHALL BE INSPECTED PRIOR TO COVERING. |
| |