Plan Review Notes
Plan Review Notes For Permit 03100662
Permit Number 03100662
Review Stop P
Sequence Number 1
Notes
Date Text
2003-11-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) THESE SPACES WERE RESIDENTIAL OCCU-
 PANCIES. AS A CHANGE OF OCCUPANCY FROM
 RESIDENTIAL TO COMMERCIAL, SECTION
 3402.2.2.1 THE BUILDING, ELECTRICAL, GAS
 MECHANICAL AND PLUMBING SYSTEMS SHALL BE
 MADE TO COMFORM TO THE INTENT OF THE
 TECHNICAL CODES AS REQUIRED BY THE BLDG.
 OFFICIAL.
 2) IF BATHING FACILITIES ARE PROVIDED ON
 A SITE THEN EACH SUCH PUBLIC OR COMMON
 USE BATHING FACILITY SHALL COMPLY WITH
 11-4.23.SECTION 11-4.1.2(6)
 SUBMIT DETAIL FOR FOR BOTH THE TOILET
 ROOM AND THE BATHING SHOWING COMPLIANCE
 WITH SECTIONS 11-4.22, & 11-4.23 AND
 ALL SUBSECTIONS. SHOW COMPLIANCE WITH
 11-4.16, 11-4.19, & 11-4.20 AND ALL SUB-
 SECTIONS. SEE FIGURES 28, 29, 32, 33, &
 34.
 3) BREAKROOM SINK SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 PROVIDE DETAILS.
 4) BATHTUB THAT WILL BE COVERED SHALL
 HAVE THE WASTE AND OVERFLOW SEALED TO
 KEEP SEWER GASSES FROM ESCAPING.
 5) ALL CAPPED WATER AND SANITARY LINES
 SHALL BE INSPECTED PRIOR TO COVERING.
  