Plan Review Notes
Plan Review Notes For Permit 03100590
Permit Number 03100590
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-14 00:00:00************ UNSAT ******************
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULE. UNABLE TO VERIFY AT THIS TIME
 IF CIRCUITS ARE SEPARATED FOR SUITES AS
 REQ'D. 215.5
  
 2)NOTE: PLEASE SEE THAT EM/EXT LTS
 APPEAR TO COMING FROM ONE PANEL ONLY?
 PLEASE CIRCUIT EM/EXT LTS OER 700.12E
  
 3)NOTE: PLEASE SHOW TRK LOADS PER 220.12
 B.
  
 4)NOTE: PLEASE CLARIFY NOTE ON PANEL
 SCHEDULE. NOTE MENTIONS, RELOCATE LTS TO
 NEW TRANSFORMER LOCATIONS? PLEASE SEE
 THAT THERE IS NOTHING SHOWN ON PLANS FOR
 THIS??
  
 PLEASE SEE NOTES FROM OTHER REVIEWERS
 THAT MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  