Plan Review Notes
Plan Review Notes For Permit 03100565
Permit Number 03100565
Review Stop M
Sequence Number 2
Notes
Date Text
2003-12-08 00:00:00PLAN CHECK - DENIED
 BOTH MODELS 1975-L & 1975-R, RETURN AIR
 JUMPER FROM THE MASTER BEDROOM NOT SIZED
 PROPERLY.PER REVISED 2001 FBC(M) 601.4
 EFFECTIVE JUNE 30, 2003, TRANSFER DUCTS
 (JUMPERS) SHALL BE 1 1/2 TIMES THE TOTAL
 SUPPLY AIR TO THE MASTER BEDROOM.THE
 DOOR SHALL HAVE A 1" CLEAR UNDERCUT.
 SEE ATTACHED AND REVISE PLANS
 ACCORDINGLY.
  