Plan Review Notes For Permit 03100565 |
Permit Number |
03100565 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-12-08 00:00:00 | PLAN CHECK - DENIED | | BOTH MODELS 1975-L & 1975-R, RETURN AIR | | JUMPER FROM THE MASTER BEDROOM NOT SIZED | | PROPERLY.PER REVISED 2001 FBC(M) 601.4 | | EFFECTIVE JUNE 30, 2003, TRANSFER DUCTS | | (JUMPERS) SHALL BE 1 1/2 TIMES THE TOTAL | | SUPPLY AIR TO THE MASTER BEDROOM.THE | | DOOR SHALL HAVE A 1" CLEAR UNDERCUT. | | SEE ATTACHED AND REVISE PLANS | | ACCORDINGLY. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|