2003-12-15 00:00:00MASTER BUILDING REVIEW CHECKLIST:
 1-ARCHITECT SELAING PLANS TO HAVE HIS
 INFORMATION ON PLANS. SEE CHAPTER
 61G1-16.004 FOR ARCHITECT'S OBLIGATION
 WHEN SUBMITTING INFORMATION FOR
 PUBLIC RECORDS.
 2-PROVIDE SPECIFIC UL ASSEMBLY FOR HOUR
 FIRE RATED GLASS BLOCK AND REVISE
 DETAIL/SPECS AS SPECIFIED ON SUCH UL
 ASSEMBLY.TABLE 600 FBC.
 3-TRUSS DRAWINGS ARE FOR ANOTHER MODEL.
 RESUBMIT AS REQUIRED.
 **NOTES: A)TRUSS ENGINEER TO SIGN, SEAL,
 DATE AND PUT HIS INFORMATION ON TRUSS
 LAYOUT AS WELL. CHAPTER 471 FL. ST.
 B)ENGINEER OF RECORD TO REVIEW TRUSS
 PACKAGE PRIOR TO SUBMITTAL.
 C)REVISE INFORMATION ON TRUSS DWGS:
 *-DESIGN CRITERIA; ADD ATTIC LIVE LOAD
 AS REQ'D BY TABLE 1604.1 FBC 2001.
 *-CODE SECTION AND GENERAL NOTES ON
 ENGINEERED TRUSSES CITE WRONG CODE.
 *UPDATE TPI REFERENCE. SEE CHAPTER
 35 FBC 2001.
  
 4-REVISE GARAGE DOOR BUCK DETAIL. HOW IS
 2 3/4" LONG TAPCON GOINT TO ALLOW 2"
 EMBEDMENT IN MASONRY IF GOING THRU 2X6
 WOOD BUCK. SEC. 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
 5-REVISE SPECIFICATIONS FOR CEILING
 INSTALLATION AT FRONT AND REAR PORCH.
 SIZE OF NAIL SPECIFIED IS TOO SHORT.
 SEE ASTM C-1063. ALSO, SPECIFY SPACING
 6-CLARIFY/REVISE DESIGN PRESSURES AT
 EXTERIOR OPENINGS. TABLES 1606.2A AND
 1606.2E FBC 2001. SOME PRESSURES WERE
 CHANGED ON SHEET 3A, BUT, NOT ON 3B.
 7-STORM SHUTTERS: A)STATEWIDE PRODUCT
 APPROVAL DOESN'T MATCH DRAWINGS.
 THERE ARE 2 DIFFERENT COMPANIES.
 B)NEED COMPLETE INSTALLATION SCHEDULE W/
 ANCHOR TYPE AND SPACING.
 C)CLEARLY MARK ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS, ANCHOR TYPE AND
 SPACING TO BE USED ACCORDING TO THE
 EDGE DISTANCE, CONNECTION TYPE, PANEL
 SPAN, DESIGN PRESSURES AND STRUCTURE
 TO BE ATTACHED TO. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 8-ENGINEER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQ'D BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 9-PROVIDE FLORIDA PRODUCT APPROVALS OR
 SITE SPECIFIC ENGINEERING FOR:
 A)GARAGE DOORS.
 B)GLASS BLOCK.
 C)DOORS AND WINDOWS. NORANDEX DRAWINGS
 DON'T MATCH FLORIDA PRODUCT APPROVAL.
 D)STRUCTURAL CONNECTORS. EG: TRUSS
 ANCHORS.
 E)WINDOW MULLIONS.
  
 10-REVISE/UPDATE TRUSS ANCHOR SCHEDULE
 AND ALL DETAILS THAT ARE AFFECTED BY
 SEC. 1609.4.3 FBC 2001 WHICH DOESN'T
 ALLOW ALLOWABLE STEEL STRESS TO BE
 INCREASED. PROVIDE CALCULATIONS FOR
 VALUES OTHER THAN THOSE PUBLISHED ON
 THE CATALOGUE. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 11-REVISE GARAGE BUCK DETAIL. HOW IS 2"
 EMBEDMENT INTO COLUMN ACHIEVED WITH
 2 3/4" TAPCON GOING THRU 2X6 BUCK?
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 12-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 13-SHEET 37: MISSING CONNECTOR AT ONE
 END OF GIRDER TRUSS AT PORCH. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)CLARIFY WHERE IS CONNECTOR EHUH 28-3
 TAKEN FROM. UNABLE TO FIND IN USP
 REVISED CATALOGUE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ @ 805-6712.