Plan Review Notes
Plan Review Notes For Permit 03100564
Permit Number 03100564
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-20 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE THAT TWO SETS OF
 ELECTRICAL PLANS WERE SUBMITTED FOR
 REVIEW UNDER THIS MASTER.
 APPEARS TO BE A LEFT HAND AND A RIGHT
 HAND.
 IT IS MY UNDERSTANDING THAT IN ORDER TO
 BE A MASTER, YOU WOULD HAVE TO HAVE LEFT
 MODEL COME IN SEPARATE FROM RH MODEL.
  
 2)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON PLANS.
  
 3)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPT(S) IN LIVING RM? AND MIDDLE BED-
 -ROOM.
  
 4)NOTE: PLEASE SEE NOTE ABOVE PANEL
 SCHEDULE. MENTIONS TO HAVE ALL BEDROOM
 AND DEN RECEPTS CON TO ARC FAULT BRKRS.
 PLEASE SEE THAT AS OF 7/1/2003 WE ARE
 NOW UNDER THE 2002 NEC AND THE REQ'MENT
 FOR ARC FAULT PROTECTION HAS EXTENDED TO
 ALL OUTLETS, INCLUDING, SD'S, LTS ETC.
 220.12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  