Notes |
Date |
Text |
2003-10-20 00:00:00 | ************* UNSAT ************** | | | | 1)NOTE: PLEASE SEE THAT TWO SETS OF | | ELECTRICAL PLANS WERE SUBMITTED FOR | | REVIEW UNDER THIS MASTER. | | APPEARS TO BE A LEFT HAND AND A RIGHT | | HAND. | | IT IS MY UNDERSTANDING THAT IN ORDER TO | | BE A MASTER, YOU WOULD HAVE TO HAVE LEFT | | MODEL COME IN SEPARATE FROM RH MODEL. | | | | 2)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS | | ON PLANS. | | | | 3)NOTE: PLEASE SEE 210.52 FOR MISSING | | RECEPT(S) IN LIVING RM? AND MIDDLE BED- | | -ROOM. | | | | 4)NOTE: PLEASE SEE NOTE ABOVE PANEL | | SCHEDULE. MENTIONS TO HAVE ALL BEDROOM | | AND DEN RECEPTS CON TO ARC FAULT BRKRS. | | PLEASE SEE THAT AS OF 7/1/2003 WE ARE | | NOW UNDER THE 2002 NEC AND THE REQ'MENT | | FOR ARC FAULT PROTECTION HAS EXTENDED TO | | ALL OUTLETS, INCLUDING, SD'S, LTS ETC. | | 220.12 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE NAY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|