 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} ADD EGRESS LIGHTING TO COMPLY WITH
 210.70(A)(2)(B), AS REDLINED ON PERMIT
 SET.
  
 2} THERE ARENO RECEPTACLES IN THE ROOM
 WITH NO DESIGNATION IN THE SOUTH EAST
 CORNER OF THE ADDITION. MUST COMPLY
 WITH 210.52(ALL).
  
 3} THE RECEPTACLE SPACING IN THE NEW
 BEDROOM DOES NOT COMPLY WITH 210.52.
  
 4} SUPPLY A LOAD CALCULATION PER 215.5.
 USE 220.3 OR 220.31 FOR CALCS, INDICATE
 THE ONE USED.
  
 5} INDICATE THE SIZE OF THE EXISTING
 SERVICE.
  
 6} THE FRAMING PLAN DOES NOT CORRELATE
 WITH THE FLOOR PLAN. CHANGE TO INDICATE
 ACTUAL CONDITIONS.
  
 7} RECEPTACLE SPACING IN THE FAMILY ROOM
 MUST COMPLY WITH 210.52.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  