Notes |
Date |
Text |
2004-05-11 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} ADD EGRESS LIGHTING TO COMPLY WITH | | 210.70(A)(2)(B), AS REDLINED ON PERMIT | | SET. | | | | 2} THERE ARENO RECEPTACLES IN THE ROOM | | WITH NO DESIGNATION IN THE SOUTH EAST | | CORNER OF THE ADDITION. MUST COMPLY | | WITH 210.52(ALL). | | | | 3} THE RECEPTACLE SPACING IN THE NEW | | BEDROOM DOES NOT COMPLY WITH 210.52. | | | | 4} SUPPLY A LOAD CALCULATION PER 215.5. | | USE 220.3 OR 220.31 FOR CALCS, INDICATE | | THE ONE USED. | | | | 5} INDICATE THE SIZE OF THE EXISTING | | SERVICE. | | | | 6} THE FRAMING PLAN DOES NOT CORRELATE | | WITH THE FLOOR PLAN. CHANGE TO INDICATE | | ACTUAL CONDITIONS. | | | | 7} RECEPTACLE SPACING IN THE FAMILY ROOM | | MUST COMPLY WITH 210.52. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|