Plan Review Notes
Plan Review Notes For Permit 03100551
Permit Number 03100551
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-23 00:00:00FAILED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 1} PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY AN
 ENGINEER ARE REQ`D PER 61G15-23.002
 TO HAVE A TITLE BLOCK.THIS AND
 SIMILAR COMMENTS, MADE REPEATEDLY,
 REGADING NON COMPLIANCE WITH ART 471 FS.
 STATUTES HAVE COMPELLED US TO START
 RETAINING ONE SET OF PLANS TO BE FILED
 AND TURNED INTO THE FPBE FOR SAID
 VIOLATIONS.
  
 2} PLEASE SHOW COMPLIANCE PER
 210.70(A)(1),IN THE NEW FAMILY ROOM.
  
 3} PLEASE NOTE ON THE PLANS COMPLIANCE
 WITH ARTICLE 210.12 NEC,FOR THE
 BEDROOMS.
  
 4} THE BEDROOMS NEED TO HAVE RECEPTACLES
 ADDED PER 210.52(A)(1) & (2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718.