Plan Review Notes
Plan Review Notes For Permit 03100551
Permit Number 03100551
Review Stop B
Sequence Number 1
Notes
Date Text
2003-10-30 00:00:00****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ADDITIONAL PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)PROVIDE AREA CALCULATIONS ON THE
 PLAN.ADDITIONS OF OVER 25% MUST COMPLY
 WITH FBC3401.7.2, 2003 AMENDMENT.
  
 4.)THE FLOOR PLAN OVERALL DIMENSION
 HAS BEEN WRITTEN OVER AND IS NOT CLEAR
 AND DOES NOT APPEAR TO MATCH THE SURVEY.
 THE DIMENSIONS MUST ADD UP TO THE TOTAL,
 AND MUST BE THE SAME AS THE SITE PLAN.
  
 5.)ENERGY CALCS, SIGNED BY BOTH THE
 PREPARER AND THE OWNER/AGENT, ARE
 REQUIRED FBC13-103.1.2.
  
 6.)THERE ARE MANY NOTES IN INK ON THE
 PLAN.THE NOTES MUST BE INITIALED BY
 THE DESIGNER OF RECORD.
  
 7.)NOTE THAT ON THE WALL SECTION YOU
 HAVE SPECIFIED R19 UNDER ATTIC, 4.2 ON
 THE WALL.IF A 600C ENERGY CALC IS
 SUMBITTED THE MINIMUM INSULATION
 REQUIRED WOULD BE R30 AND R5
 RESPECTIVELY.
  
 8.)CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC1804.1.7, LOWEST BUILDING
 FLOOR ELEVATION AT THE PERIMITER OF
 A MONOLITHIC FOUNDATION AT HABITABLE
 AREAS SHALL BE A MINIMUM OF 4" ABOVE THE
 FINISHED GRADE.SHOW ON WALL SECTION.
  
 9.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025 FOR MORE
 INFORMATION.
  
 10.) TWO COPIES OF ALL DOCUMENTS MUST
 BE SUBMITTED.ONE WILL BE RETAINED AT
 THE CITY AND ONE WILL BE YOUR PERMIT
 SET.
  
 11.) ADDITIONAL FEES MAY BE DUE.THESE
 FEES WILL BE DETERMINED AFTER AREA
 CALCULATIONS ARE SUBMITTED ON THE PLAN.
  
 12.) THIS JOB IS A SUBSTANTIAL
 IMPROVEMENT TO A RESIDENCE LOCATED IN A
 FLOOD ZONE. CITY OF WEST PALM BEACH
 MUNICIPAL CODE REQUIRES THAT THE
 LOWEST FLOOR BE ELEVATED TO 6" ABOVE THE
 BASE FLOOD ELEVATION, 94-546.PROVIDE
 AN ELEVATION CERTIFICATE FOR THE
 EXISTING HOUSE AND SHOW COMPLIANCE ON
 THE PLAN.
  
 13.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 14.)A TITLE BLOCK FOR THE ENGINEER
 IS REQUIRED, FAC61G15-23.001.
  
 15.)GABLE ENDS ARE TO BE STRUCTURALLY
 CONTINUOUS, FBC2117.1.
  
 16.)A STATEWIDE OR LOCAL PRODUCT
 APPROVAL IS REQUIRED FOR WINDOWS, DOORS,
 TRUSS ANCHORS AND IMPACT PROTECTION,
 FAC9B-72.SEE THE DCA WEBSITE,
 WWW.DCA.STATE.FL.US/FHCD/FBC/COMMITTEES/
 PRODUCT_APPROVAL/1_PRODUCT_APPROVAL.HTM
 FOR MORE INFORMATION.
  
 17.)THERE IS A NOTE ON THE PLAN TO
 "MAKE EXIST WINDOW COMPLY W/EGRESS".
 SHOW HOW THIS COMPLIES WITH FBC1005.4
 BY GIVING THE WINDOW SIZE AND TYPE.
  
 18.)IMPACT PROTECTION REQUIRED FBC
 1606.1.4.
  
 19.)THERE IS A REFERENCE TO SBC (NOTE
 AT THE WALL SECTION); CURRENT CODE IS
 FBC.
  
 20.)ATTIC ACCESS REQUIRED TO COMPLY
 WITH FBC2309.
  
 21.)PROVIDE A HURRICANE SHUTTER
 INSTALLATION SCHEDULE IF SHUTTERS ARE TO
 BE USED, SEE ATTACHED.