2003-10-14 00:00:00 | ******** UNSAT ***************** |
| |
| 1)NOTE: PLEASE CORRELATE PLANS SUBMITTED |
| FOR REVIEW AND PERMITTING. |
| ONE SET FROM ARCH MENTIONS ; SERVICE TO |
| FEED SPORTS LIGHTING? YET, E-PLANS |
| SUBMITTED BY ENGINEER SHOWS A COMPLETELY |
| DIFFERENT SERVICE AND MENTIONS THAT |
| SERVICE FEDDING SPORTS LIGHTING? |
| PLEASE EITHER CORRELATE PLANS OR IF |
| INDEED THESE ARE TWO SEPARATE AREAS, |
| PLEASE CLARIFY AND PERMIT SEPARATELY IF |
| NEED BE. |
| |
| 2)NOTE: PLEASE SEE SERVICE ONE, PLEASE |
| SEE MISSING GROUNDING ELECTRODE CONDUCT- |
| -OR PER 250.24/250.66 ETC? |
| |
| 3)NOTE: PLEASE SHOW CIRCUITING AND |
| CORRELATE WITH A SUBMITTED PANEL |
| SCHEDULE. |
| |
| 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| AT 125%. 215.3/230.42 ETC. |
| |
| 5)NOTE: PLEASE SEE THAT RISER MENTIONS; |
| NEW METER AND PLANS MENTIONS EXIST TO |
| REMAIN? |
| |
| 6)NOTE: PLEASE SEE SERVICE #2, SHOW ALL |
| CONTINUOUS LOADS AT 125%. 215.3/230.42 |
| ETC. |
| PLEASE ALSO CLARIFY AND CORRELATE? |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |