Plan Review Notes For Permit 03100513 |
Permit Number |
03100513 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-10 00:00:00 | PROVISO: | | ATTIC ACCESS OPENING SHALL BE NO LESS | | THAN 30" X 22" AS PER 2001 FBC(M) 306.3 | | | | 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 - | | 1. THE SERVICE PANEL OF THE EQUIPMENT IS | | LOCATED WITHIN 6 FT OF AN ATTIC | | ACCESS. | | 2. A DEVICE IS INSTALLED TO ALERT THE | | OWNER OR SHUT DOWN WHEN THE | | CONDENSATE DRAIN IS NOT WORKING | | PROPERLY. | | 4. A NOTICE IS POSTED ON THE ELECTRIC | | SERVICE PANEL INDICATING TO THE | | HOMEOWNER THAT THE AIR HANDLER IS | | LOCATED IN THE ATTIC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|