Plan Review Notes
Plan Review Notes For Permit 03100434
Permit Number 03100434
Review Stop M
Sequence Number 4
Notes
Date Text
2005-05-02 00:00:00PROVISO:
 RETAIL SPACE "C4" - PLEASE NOTE THE
 LOCATION OF THE OUTSIDE AIR INTAKE IN
 RELATION TO THE DISCHARGE FROM THE
 CONDENSING UNIT.OUTSIDE AIR SHALL BE
 LOCATED AS TO NOT RECIRCULATE THE
 HEAT/EXHAUST AIR FROM THE CONDENSING
 UNIT.O.A. INTAKE SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM ALLEYS, PARKING OR
 LOADING AREAS.2001 FBC/M 401.5.1
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.