Plan Review Notes
Plan Review Notes For Permit 03100434
Permit Number 03100434
Review Stop P
Sequence Number 3
Notes
Date Text
2005-04-23 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT P.1 PIPING TO 2" RISER UPSTREAM
 OF THE TOILET ROOMS OF RETAIL C1 NOT
 SHOWN. DRINKING FOUNTAINS ARE NOT SHOWN
 FOR RETAIL SPACES 2, 3, & 4, PLEASE
 CLARIFY. SECTION 104.2.1.
 2) SANT. RISER DIAGRAM DOES NOT REFLECT
 THE PIPING LAYOUT SHOWN ON SHT P.1, AND
 RISER DIAGRAM SHALL BE AN ISOMETRIC FORM
 SHOWING ALL PIPE SIZES, VENTING ECT.
 3) A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL DRAWINS. FAC 61G1-16.004 &
 FS 481.2055. THESE ARE NOT ON THE RISER
 DIAGRAMS SUBMITTED.
  
  
 REVIEW BY KEN STEVENS