2004-01-08 00:00:00DENIED:
 RESIDENTIAL:
 1.PER 2001 FBC(M) 403.3, VENTILATION
 SYSTEMS, FOR OTHER THAN R-3 (ONE & TWO
 FAMILY DWELLINGS), SHALL BE DESIGNED TO
 SUPPLY THE MINIMUM OUTSIDE AIR IN
 ACCORDANCE WITH TABLE 403.3.PLEASE
 PROVIDE OUTSIDE AIR CALCULATIONS.
 INDICATE OUTSIDE AIR DUCT SIZE,
 MATERIAL, LAYOUT AND INTAKE ON THE PLAN.
  
 2.PLAN SHEET AC.3 INDICATES DUCT TO
 2ND FLOOR IN RATED SHAFT. PLEASE
 PROVIDE SHAFT DETAIL.
  
 RETAIL:PLANS ARE CODE COMPLIANT.
  
 PLEASE NOTE:
 PLANS DO NOT INDICATE THE USE OF THE
 RETUAIL SPACE.BECAUSE OF THE LOCATION
 AND PROOPERTY LINES, ALLOWANCE FOR A
 RESTAURANT MAY BE DIFFICULT SHOULD
 CONSIDERATION NOT BE GIVEN FOR THE
 INSTALLATION OF GREASE DUCT NOT BE MADE
 AT THE BEGINNING OF CONSTURCTION.
  