Plan Review Notes For Permit 03100434 |
Permit Number |
03100434 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-01-07 00:00:00 | ************ PROVISO ************** | | | | 1)NOTE: NEW SERVICE IS NOW SHOWN AND | | AIC RATINGS FOR APTS ETC ARE SHOWN , | | HOWEVER, THIS IS NOT SHOWN FOR 1000A MCB | | PER 110.9 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|