2004-01-14 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| **BUILDING H** |
| **NOTE: READ THESE COMMENTS INDIVIDUALLY |
| THEY ARE NOT EXACTLY THE SAME AS THE |
| COMMENTS FOR BUILDING G** |
| |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 11/18/03: |
| |
| 1) THE NOTICE OF COMMENCEMENT SHALL BE |
| RECORDED AT PALM BEACH COUNTY COURTHOUSE |
| AND A COPY SUBMITTED TO THIS OFFICE |
| BEFORE A PERMIT CAN BE ISSUED.BLANK |
| FORMS ARE AVAILABLE FROM THIS OFFICE. |
| |
| 3) 61G1-16.004FL. ADMIN. CODE.SHEET |
| A.1 HAS A TITLE BLOCK THAT INCLUDES ONLY |
| THE ARCHITECT'S LICENSE NUMBER AR0014128 |
| WHILE SHEETS A.2 TO A.23 ALL INCLUDE |
| ONLY THE FIRM'S LICENSE NUMBER |
| AA26000691. EACH SHEET SHALL INCLUDE |
| BOTH LICENSE NUMBERS.THE MISSING |
| LICENSE NUMBERS MAY BE HANDWRITTEN ON |
| THE PLANS. |
| |
| 5) FBC 13-103.1.2THIS COMMENT HAS NOT |
| BEEN PROPERLY ADDRESSED. THE ONLY ENERGY |
| CODE COMPLIANCE FORM THAT HAS BEEN |
| SIGNED IS THE FIRST/TOP ONE IN EACH |
| PACKAGE (I.E. RESIDENTIAL UNIT 64). NONE |
| OF THE OTHER RESIDENTIAL UNITS OR THE |
| COMMERCIAL UNITS HAVE THE ENERGY FORMS |
| SIGNED BY THE BUILDING OWNER, THE |
| OWNER'S ARCHITECT OR OTHER AUTHORIZED |
| AGENT LEGALLY DESIGNATED BY THE OWNER. |
| |
| 6) FBC 13-103.1.2AS STATED IN COMMENT |
| NUMBER (5) ABOVE, THE ENERGY CODE |
| COMPLIANCE FORMS FOR THE COMMERCIAL |
| UNITS HAVE NOT BEEN SIGNED BY THE |
| BUILDING OWNER, OWNER'S ARCHITECT OR |
| OTHER AUTHORIZED AGENT LEGALLY |
| DESIGNATED BY THE OWNER. |
| |
| 11) FBC 1606.2.4SHEET S4.0, WOOD TRUSS |
| CONNECTOR MARK D IS STATED AS HAVING AN |
| UPLIFT CAPACITY OF 1490#.THE SIMPSON |
| HETA 20 WITH 10-10DX1-1/2 NAILS HAS A |
| CAPACITY OF 1240#.AMEND THE PLAN. |
| |
| 12) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| FBC 1006.2.4SHEET A.7, NORTH ELEVATION |
| AND EAST ELEVATION.THERE ARE WINDOWS |
| WITHIN 10 FT VERTICALLY OF THE EXTERIOR |
| EXIT STAIR.THESE WINDOWS SHALL BE 3/4 |
| HOUR FIRE-RATED ASSEMBLIES.AMEND THE |
| PLANS. |
| |
| 13) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| FBC 1005.4THE THIRD FLOOR BEDROOM IN |
| RESIDENTIAL UNIT 67 IS SHOWN ON SHEET |
| A.4 AS HAVING WINDOW TYPE H.AN |
| EMERGENCY EGRESS WINDOW IS REQUIRED. THE |
| WINDOW SCHEDULE ON SHEET A.20 STATES |
| THAT TYPE H IS A SINGLE HUNG WINDOW, BUT |
| THE ELEVATION DOES NOT SHOW IT AS SINGLE |
| HUNG.CLARIFY THE PROPOSED WINDOW TYPE |
| TO ENSURE THE EGRESS WINDOW REQUIREMENTS |
| ARE MET. |
| |
| 14) PRODUCT APPROVALS |
| THE PROPOSED PRODUCTS SHALL HAVE STATE- |
| WIDE OR LOCAL PRODUCT APPROVAL IN |
| ACCORDANCE WITH RULE 9B-72 FAC (FOR |
| STATEWIDE PRODUCT APPROVAL SEE |
| WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP): |
| (A) THE DOOR SCHEDULE, SHEET A.19, |
| STATES THAT DOORS 10, 16, 22, 28 & 33 |
| (SECOND FLOOR ENTRANCE DOORS TO THE |
| RESIDENTIAL UNITS) ARE TO BE IMPACT |
| RATED.THE SUBMITTED PRODUCT APPROVAL |
| NOA# 02-0109.03 WHICHIS FOR NON-RATED |
| FIBERGLASS DOORS.SUBMIT THREE COPIES |
| OF A PRODUCT APPROVAL FOR AN ALTERNATIVE |
| DOOR. |
| NOTE: PRINT AND ATTACH THE RELEVANT |
| STATEWIDE PRODUCT APPROVAL LISTING |
| REFERENCE SHEET FL### (FOR EXAMPLE, SEE |
| SHEET ATTACHED TO EACH OF THE SUBMITTED |
| PRODUCT APPROVALS, DURING PLAN REVIEW, |
| TO EXPEDITE PERMIT ISSUE). |
| |
| 16) FBC* 105.3RESIDENT INSPECTOR. |
| SUBMIT INSPECTOR RESUME' AND LICENSE |
| DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF |
| RESIDENT INSPECTOR PROGRAM.A |
| RESIDENT INSPECTOR PROGRAM IS REQUIRED, |
| ON THIS PROJECT, DUE TO THE BUILDING |
| BEING OVER 2 STORIES IN HEIGHT. |
| |
| 17) CONDOMINIUM V APARTMENTS.IF THE |
| DWELLING UNITS ARE TO BE SOLD AS |
| CONDOMINIUMS, NO CERTIFICATE OF |
| OCCUPANCY CAN BE ISSUED UNTIL A |
| 'DECLARATION OF CONDOMINIUM' HAS BEEN |
| SUBMITTED TO THE STATE FOR APPROVAL, AND |
| THEN RECORDED WITH THE CLERK OF THE |
| COUNTY COURT.A RECORDED COPY SHALL BE |
| SUBMITTED TO THE CITY FOR RECORDS, |
| ADDRESSING PURPOSES, AND NOTIFICATION OF |
| PALM BEACH COUNTY PROPERTY APPRAISER'S |
| OFFICE. |
| |
| 18) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| OLD SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHALL BE INCLUDED WITH THE |
| RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |