2004-01-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 **BUILDING H**
 **NOTE: READ THESE COMMENTS INDIVIDUALLY
 THEY ARE NOT EXACTLY THE SAME AS THE
 COMMENTS FOR BUILDING G**
  
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 11/18/03:
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 3) 61G1-16.004FL. ADMIN. CODE.SHEET
 A.1 HAS A TITLE BLOCK THAT INCLUDES ONLY
 THE ARCHITECT'S LICENSE NUMBER AR0014128
 WHILE SHEETS A.2 TO A.23 ALL INCLUDE
 ONLY THE FIRM'S LICENSE NUMBER
 AA26000691. EACH SHEET SHALL INCLUDE
 BOTH LICENSE NUMBERS.THE MISSING
 LICENSE NUMBERS MAY BE HANDWRITTEN ON
 THE PLANS.
  
 5) FBC 13-103.1.2THIS COMMENT HAS NOT
 BEEN PROPERLY ADDRESSED. THE ONLY ENERGY
 CODE COMPLIANCE FORM THAT HAS BEEN
 SIGNED IS THE FIRST/TOP ONE IN EACH
 PACKAGE (I.E. RESIDENTIAL UNIT 64). NONE
 OF THE OTHER RESIDENTIAL UNITS OR THE
 COMMERCIAL UNITS HAVE THE ENERGY FORMS
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 6) FBC 13-103.1.2AS STATED IN COMMENT
 NUMBER (5) ABOVE, THE ENERGY CODE
 COMPLIANCE FORMS FOR THE COMMERCIAL
 UNITS HAVE NOT BEEN SIGNED BY THE
 BUILDING OWNER, OWNER'S ARCHITECT OR
 OTHER AUTHORIZED AGENT LEGALLY
 DESIGNATED BY THE OWNER.
  
 11) FBC 1606.2.4SHEET S4.0, WOOD TRUSS
 CONNECTOR MARK D IS STATED AS HAVING AN
 UPLIFT CAPACITY OF 1490#.THE SIMPSON
 HETA 20 WITH 10-10DX1-1/2 NAILS HAS A
 CAPACITY OF 1240#.AMEND THE PLAN.
  
 12) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 1006.2.4SHEET A.7, NORTH ELEVATION
 AND EAST ELEVATION.THERE ARE WINDOWS
 WITHIN 10 FT VERTICALLY OF THE EXTERIOR
 EXIT STAIR.THESE WINDOWS SHALL BE 3/4
 HOUR FIRE-RATED ASSEMBLIES.AMEND THE
 PLANS.
  
 13) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 1005.4THE THIRD FLOOR BEDROOM IN
 RESIDENTIAL UNIT 67 IS SHOWN ON SHEET
 A.4 AS HAVING WINDOW TYPE H.AN
 EMERGENCY EGRESS WINDOW IS REQUIRED. THE
 WINDOW SCHEDULE ON SHEET A.20 STATES
 THAT TYPE H IS A SINGLE HUNG WINDOW, BUT
 THE ELEVATION DOES NOT SHOW IT AS SINGLE
 HUNG.CLARIFY THE PROPOSED WINDOW TYPE
 TO ENSURE THE EGRESS WINDOW REQUIREMENTS
 ARE MET.
  
 14) PRODUCT APPROVALS
 THE PROPOSED PRODUCTS SHALL HAVE STATE-
 WIDE OR LOCAL PRODUCT APPROVAL IN
 ACCORDANCE WITH RULE 9B-72 FAC (FOR
 STATEWIDE PRODUCT APPROVAL SEE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP):
 (A) THE DOOR SCHEDULE, SHEET A.19,
 STATES THAT DOORS 10, 16, 22, 28 & 33
 (SECOND FLOOR ENTRANCE DOORS TO THE
 RESIDENTIAL UNITS) ARE TO BE IMPACT
 RATED.THE SUBMITTED PRODUCT APPROVAL
 NOA# 02-0109.03 WHICHIS FOR NON-RATED
 FIBERGLASS DOORS.SUBMIT THREE COPIES
 OF A PRODUCT APPROVAL FOR AN ALTERNATIVE
 DOOR.
 NOTE: PRINT AND ATTACH THE RELEVANT
 STATEWIDE PRODUCT APPROVAL LISTING
 REFERENCE SHEET FL### (FOR EXAMPLE, SEE
 SHEET ATTACHED TO EACH OF THE SUBMITTED
 PRODUCT APPROVALS, DURING PLAN REVIEW,
 TO EXPEDITE PERMIT ISSUE).
  
 16) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO THE BUILDING
 BEING OVER 2 STORIES IN HEIGHT.
  
 17) CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, NO CERTIFICATE OF
 OCCUPANCY CAN BE ISSUED UNTIL A
 'DECLARATION OF CONDOMINIUM' HAS BEEN
 SUBMITTED TO THE STATE FOR APPROVAL, AND
 THEN RECORDED WITH THE CLERK OF THE
 COUNTY COURT.A RECORDED COPY SHALL BE
 SUBMITTED TO THE CITY FOR RECORDS,
 ADDRESSING PURPOSES, AND NOTIFICATION OF
 PALM BEACH COUNTY PROPERTY APPRAISER'S
 OFFICE.
  
 18) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]