Plan Review Notes
Plan Review Notes For Permit 03100434
Permit Number 03100434
Review Stop P
Sequence Number 1
Notes
Date Text
2003-11-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P.1 PLUMBING NOTES #15, WATTS
 530C NOT APPROVED FOR MULTI-HEATER USE
 PER MANUFACTURE INFORMATION. WATTS 530
 APPROVED FOR INDIVIDUAL HEATER USE ONLY.
 PROVIDE INFORMATION FOR THERMAL EXPANS-
 ION CONTROL PER 607.3.2. ALSO SEE WATER
 RISER DETAIL SHT P.4 AND WATER HEATER
 DETAIL SHT P.5.
 2) SHT P.4 WATER HAMMER ARRESTORS ARE
 REQUIRED PER SECTION 604.9 FOR WASH
 MACHINES, DISHWASHERS, AND ICE MAKERS.
 SHOW WATER HAMMER ARRESTORS ON THE WATER
 RISER LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING.
 MANUF. INSTALLATION INSTRUCTIONS AND
 PDI-WH 201.
 3) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICES.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692