Plan Review Notes
Plan Review Notes For Permit 03100434
Permit Number 03100434
Review Stop M
Sequence Number 1
Notes
Date Text
2003-11-04 00:00:00DENIED: BUILDING H
 1.OUTSIDE AIR REQUIRED AS PER 2001
 FBC(M) TABLE 403.3.
  
 2. CEILING FIRE DAMPERS REQUIRED AS
 DICTATED BY BUILDING CONSTRUCTION, SEE
 1 HR RATED ASSEMBLY ON PLAN SHEET A.12.
 SEE ALSO DETAIL 15 ON PLAN SHEET A.16.
 PLEASE INDICATE LOCATION OF DAMPERS AS
 REQUIRED PER 2001 FBC(M) 607.6.
  
 3. ATTIC ACCESS OPENING SHALL BE NO LESS
 THAN 30" X 22" AS PER 2001 FBC(M) 306.3
 ATTIC INSTALLATION REQUIREMENTS:
 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 -
 1. THE SERVICE PANEL OF THE EQUIPMENT IS
 LOCATED WITHIN 6 FT OF AN ATTIC
 ACCESS.THE PASSAGEWAY SHALL NOT BE
 LESS THAN 24" WIDE AND HAVE A SOLID
 AND CONTINUOUS FLOORING.
 2. A DEVICE IS INSTALLED TO ALERT THE
 OWNER OR SHUT DOWN WHEN THE
 CONDENSATE DRAIN IS NOT WORKING
 PROPERLY.
 4. A NOTICE IS POSTED ON THE ELECTRIC
 SERVICE PANEL INDICATING TO THE
 HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC.
  
 4. PLEASE CLARIFY PLAN SHEET A.2 FLOOR
 PLAN NOTE #10 DRYER VENT ABOVE GARAGE
 DOOR.PLANS DO NOT INDICATE A GARAGE.
  
 5. PLAN SHEET AC.2 INDICATES EXHAUST
 DUCT PENETRATING FLOOR AND THROUGH TO
 THE SECOND FLOOR.WILL THIS DUCT BE
 IN A RATED SHAFT BEING IT IS PENETRATING
 A FIRE RATED ASSEMBLY?
  
 RETAIL:
 1. FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE AS PER
 2001 FBC(M) 606.2.1 & NFPA 90A 4-4.4.3.
  
 2. PLAN DO NOT INDICATE USE OF THE
 RETAIL SPACE.BECAUSE OF THE LOCATION
 AND PROPERTY LINES, ALLOWANCE FOR A
 RESTAURANT MAY BE DIFFICULT SHOULD
 CONSIDERATION NOT BE GIVEN FOR THE
 INSTALLATION OF GREASE DUCT NOT BE MADE
 AT THE BEGINNING OF CONSTRUCTION.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved