Date |
Text |
2003-11-04 00:00:00 | DENIED: BUILDING H |
| 1.OUTSIDE AIR REQUIRED AS PER 2001 |
| FBC(M) TABLE 403.3. |
| |
| 2. CEILING FIRE DAMPERS REQUIRED AS |
| DICTATED BY BUILDING CONSTRUCTION, SEE |
| 1 HR RATED ASSEMBLY ON PLAN SHEET A.12. |
| SEE ALSO DETAIL 15 ON PLAN SHEET A.16. |
| PLEASE INDICATE LOCATION OF DAMPERS AS |
| REQUIRED PER 2001 FBC(M) 607.6. |
| |
| 3. ATTIC ACCESS OPENING SHALL BE NO LESS |
| THAN 30" X 22" AS PER 2001 FBC(M) 306.3 |
| ATTIC INSTALLATION REQUIREMENTS: |
| 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 - |
| 1. THE SERVICE PANEL OF THE EQUIPMENT IS |
| LOCATED WITHIN 6 FT OF AN ATTIC |
| ACCESS.THE PASSAGEWAY SHALL NOT BE |
| LESS THAN 24" WIDE AND HAVE A SOLID |
| AND CONTINUOUS FLOORING. |
| 2. A DEVICE IS INSTALLED TO ALERT THE |
| OWNER OR SHUT DOWN WHEN THE |
| CONDENSATE DRAIN IS NOT WORKING |
| PROPERLY. |
| 4. A NOTICE IS POSTED ON THE ELECTRIC |
| SERVICE PANEL INDICATING TO THE |
| HOMEOWNER THAT THE AIR HANDLER IS |
| LOCATED IN THE ATTIC. |
| |
| 4. PLEASE CLARIFY PLAN SHEET A.2 FLOOR |
| PLAN NOTE #10 DRYER VENT ABOVE GARAGE |
| DOOR.PLANS DO NOT INDICATE A GARAGE. |
| |
| 5. PLAN SHEET AC.2 INDICATES EXHAUST |
| DUCT PENETRATING FLOOR AND THROUGH TO |
| THE SECOND FLOOR.WILL THIS DUCT BE |
| IN A RATED SHAFT BEING IT IS PENETRATING |
| A FIRE RATED ASSEMBLY? |
| |
| RETAIL: |
| 1. FAN SHUTDOWN BY DUCT SMOKE DETECTOR |
| WITH NOTIFICATION TO ALARM/STROBE AS PER |
| 2001 FBC(M) 606.2.1 & NFPA 90A 4-4.4.3. |
| |
| 2. PLAN DO NOT INDICATE USE OF THE |
| RETAIL SPACE.BECAUSE OF THE LOCATION |
| AND PROPERTY LINES, ALLOWANCE FOR A |
| RESTAURANT MAY BE DIFFICULT SHOULD |
| CONSIDERATION NOT BE GIVEN FOR THE |
| INSTALLATION OF GREASE DUCT NOT BE MADE |
| AT THE BEGINNING OF CONSTRUCTION. |