Plan Review Notes For Permit 03100434 |
Permit Number |
03100434 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-31 00:00:00 | 1) PLEASE CONFIRM THAT THIS BUILDING | | AND 1930 SOUTH DIXIE HIGHWAY ARE | | NOT LOCATED IN THE CITY FIRE LIMITS. | | CERTAIN RESTRICTIONS APPLY. | | | | 2) NO FIRE SPRINKLER DRAWINGS PROVIDED | | WITH PLANS. BUILDING IS REQUIRED TO BE | | FIRE SPRINKLER PROTECTED PER FS | | 553.895(2). | | | | 3) NO FIRE ALARM PLANS PROVIDED WITH | | THE DRAWINGS. THE REQUIRED FIRE | | SPRINKLER SYSTEM IS REQUIRED TO BE | | MONITORED. | | | | 4) BUILDING ADDRESS IS REQUIRED. | | | | 5) PLEASE INDICATE PRESCRIPTIVE | | STRENGTH REQUIREMENTS FOR HANDRAILS. | | | | 6) UNIT ENTRY DOORS ARE TO BE AT | | LEAST 20 MINUTE FIRE RATED. | | | | 7) PORTABLE FIRE EXTINGUISHERS ARE | | REQUIRED. | | | | 8) EMERGENCY LIGHTS FOR EXTERIOR STAIRS. | | | | 9) HANDRAILS REQUIRED ON BOTH SIDES | | OF THE STAIRS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|