Plan Review Notes
Plan Review Notes For Permit 03100434
Permit Number 03100434
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-10-31 00:00:001) PLEASE CONFIRM THAT THIS BUILDING
 AND 1930 SOUTH DIXIE HIGHWAY ARE
 NOT LOCATED IN THE CITY FIRE LIMITS.
 CERTAIN RESTRICTIONS APPLY.
  
 2) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. BUILDING IS REQUIRED TO BE
 FIRE SPRINKLER PROTECTED PER FS
 553.895(2).
  
 3) NO FIRE ALARM PLANS PROVIDED WITH
 THE DRAWINGS. THE REQUIRED FIRE
 SPRINKLER SYSTEM IS REQUIRED TO BE
 MONITORED.
  
 4) BUILDING ADDRESS IS REQUIRED.
  
 5) PLEASE INDICATE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR HANDRAILS.
  
 6) UNIT ENTRY DOORS ARE TO BE AT
 LEAST 20 MINUTE FIRE RATED.
  
 7) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 8) EMERGENCY LIGHTS FOR EXTERIOR STAIRS.
  
 9) HANDRAILS REQUIRED ON BOTH SIDES
 OF THE STAIRS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910