Plan Review Notes
Plan Review Notes For Permit 03100434
Permit Number 03100434
Review Stop E
Sequence Number 1
Notes
Date Text
2003-11-03 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE SEE PLANS REFERENCE THE
 99 NEC AND WE ARE NOW UNDER THE 2002 NEC
 AS OF 7-1-03.
 PLEASE ADJUST PLANS.
  
 2)NOTE: PLEASE ALSO SEE THE REQUIREMENT
 FOR ARC FAULT PROTECTION HAS ALSO CHANGE
 -D PER 210.12
  
 3)NOTE: PLEASE SHOW RECEPT REQ'D PER
 210.62 FOR "SHOW" WINDOW RECEPTS. FIRST
 FLR.
  
 4)NOTE: PLEASE CHECK RECEPT SPACING PER
 210.52
  
 5)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER NEC 220. PLEASE ALSO SHOW ALL
 CONTINUOUS LOADS AT 125%. 215.3/230.42
 ETC.
  
 6)NOTE: PLEASE SIZE SEC'S PER 310.16 AND
 SERVICE SIZE. THERE IS NO OCP TO LIMIT
 SERVICE TO 600A'S. LOAD IS ALREADY
 SHOWN AT 593A AND CONDUCTORS ARE ONLY
 RATED FOR 610A'S AND TOTAL SERVICE
 PROVIDE FOR BLDG ANF UNITS IS OVER 900A'
 -S.? 230.42 ETC.
  
 7)NOTE: PLEASE SIZE GEC TO FOOTER STEEL
 PER 250.66 AND CONNECTION PER 250.50
  
 8)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 THAT WILL HAVE AN AFFECT ON ELECTRICAL
 PLANS. PLEASE ALSO SEE 700.12E FOR
 CIRCUITING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]