2003-11-18 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) THE NOTICE OF COMMENCEMENT SHALL BE |
| RECORDED AT PALM BEACH COUNTY COURTHOUSE |
| AND A COPY SUBMITTED TO THIS OFFICE |
| BEFORE A PERMIT CAN BE ISSUED.BLANK |
| FORMS ARE AVAILABLE FROM THIS OFFICE. |
| |
| 2) IMPACT FEES. THE PLANS SHALL BE TAKEN |
| TO PALM BEACH COUNTY BUILDING DEPARTMENT |
| FOR IMPACT FEE ASSESSMENT. THEY SHALL BE |
| STAMPED AT THAT OFFICE AND A COPY OF THE |
| PAID RECEIPT SUBMITTED TO THE CITY OF |
| WEST PALM BEACH DEPT OF CONSTRUCTION |
| SERVICES BEFORE A PERMIT CAN BE ISSUED. |
| |
| 3) 61G1-16.004(6) FACTHE TITLE BLOCK |
| ON THE ARCHITECTURAL PLANS SHALL INCLUDE |
| THE PRINTED NAME OF THE ARCHITECT |
| SEALING THE DOCUMENT. |
| |
| 4) FBC* 104.2.4SITE SURVEY.A SIGNED |
| AND SEALED SURVEY DRAWING PREPARED BY A |
| QUALIFIED SURVEYOR IS REQUIRED (REF: |
| 472.025(1) FL. STATUTES) |
| |
| 5) FBC 13-103.1.2THE SUBMITTED ENERGY |
| CODE COMPLIANCE FORMS FOR THE |
| RESIDENTIAL UNITS SHALL BE SIGNED BY THE |
| BUILDING OWNER, THE OWNER'S ARCHITECT OR |
| OTHER AUTHORIZED AGENT LEGALLY |
| DESIGNATED BY THE OWNER. |
| |
| 6) FBC 13-101.1.6NO ENERGY CODE |
| COMPLIANCE FORMS HAVE BEEN SUBMITTED |
| FOR THE FIRST FLOOR COMMERCIAL UNITS. |
| THE WHOLE BUILDING (INCL. FUTURE TENANT |
| SPACE) SHALL BE CONSIDERED.SHELL |
| BUILDINGS SHALL BE SHOWN TO COMPLY WITH |
| METHOD B (SEE SUB-CHAPTER 4).ALL |
| ASSUMPTIONS MADE ABOUT SYSTEMS, NOT |
| SHOWN ON THE CURRENT PLANS, SHALL BE |
| LISTED AND APPENDED TO THE FORM 400B FOR |
| SUBMITTAL.THIS WILL BE COMPARED TO THE |
| ACTUAL SYSTEMS PROPOSED, AT A LATER, FOR |
| INSTALLATION BY THE TENANT(S).THE |
| ASSUMPTIONS LISTED ON THE APPENDIX SHEET |
| SHALL BE AT LEAST THE MINIMUM STANDARD |
| (LIGHTING, HVAC ETC) TO ALLOW THE WHOLE |
| BUILDING TO BE OCCUPIED FOR IT'S |
| INTENDED PURPOSE. |
| |
| 7) FBC* F102.2.4ROOF COVERING IN THE |
| FIRE DISTRICT.ANNOTATE THE PLANS TO |
| SPECIFY FIRE BARRIER BOARD AND AN |
| APPROPRIATE UNDERLAYMENT TO ACHIEVE THE |
| REQUIRED CLASS A OR B RATING. |
| |
| 8) FBC* F102.2.7ARCHITECTURAL TRIM ON |
| BUILDINGS IN THE FIRE DISTRICT SHALL BE |
| CONSTRUCTED OF APPROVED NON-COMBUSTIBLE |
| MATERIALS OR FIRE RETARDANT TREATED |
| WOOD.THE ELEVATIONS SHOW P.T. CEDAR |
| WOOD SHAKE SIDING AND FASCIA, DECORATIVE |
| WOOD TRELLIS MEMBERS AND OUTRIGGERS, AND |
| WOOD BEAMS.AMEND THE PLANS TO |
| DEMONSTRATE COMPLIANCE. |
| |
| 9) FBC*F102.2.8THE CANVAS AWNING |
| SUPPORTS SHALL BE OF NON-COMBUSTIBLE |
| MATERIALS AND THE COVERING SHALL BE |
| FLAME RESISTANT AS DETERMINED IN |
| ACCORDANCE WITH FBC 3103.1.AMEND THE |
| PLANS TO DEMONSTRATE COMPLIANCE. |
| |
| 10) FBC 1604.1SHEET S0.2, |
| PRE-ENGINEERED WOOD TRUSSES NOTE 4.THE |
| TRUSSES SHALL BE DESIGNED FOR A BOTTOM |
| CHORD LIVE LOAD NOT LESS THAN 10 PSF |
| (RESIDENTIAL ATTICS WITHOUT STORAGE). |
| ANNOTATE THE PLANS TO COMPLY. |
| |
| 11) FBC 1606.2.4SHEET S4.0, WOOD TRUSS |
| CONNECTION MARK B AND C (DOUBLE ANCHORS) |
| ARE STATED AS HAVING TWICE THE UPLIFT |
| CAPACITY OF A SINGLE ANCHOR.THIS IS |
| NOT CORRECT FOR EMBEDDED ANCHORS SUCH |
| HETA & HHETA BECAUSE THE FAILURE MODE IS |
| INFLUENCED BY OVERLAPPING OF THE |
| CONCRETE 'PULL-OUT CONES' FOR THE TWO |
| ANCHORS (SEE 2003 SIMPSON CATALOGUE). |
| AMEND THE SCHEDULE. |
| |
| 12) FBC 1006.2.4SHEET A.7, NORTH |
| ELEVATION AND EAST ELEVATION.THERE ARE |
| WINDOWS WITHIN 10 FT VERTICALLY OF THE |
| EXTERIOR EXIT STAIR.THESE WINDOWS |
| SHALL BE 3/4 HOUR RATED ASSEMBLIES. |
| AMEND THE PLANS |
| |
| 13) FBC 1005.4THE THIRD FLOOR BEDROOM |
| IN RESIDENTIAL UNIT 67 IS SHOWN ON SHEET |
| A.4 AS HAVING WINDOW TYPE H.AN |
| EMERGENCY EGRESS WINDOW IS REQUIRED. |
| THE WINDOW SCHEDULE ON SHEET A.20 STATES |
| THAT TYPE H IS A SINGLE HUNG WINDOW BUT |
| THE ELEVATION DOES NOT SHOW IT AS SINGLE |
| HUNG.CLARIFY THE PROPOSED WINDOW TYPE |
| TO ENSURE THE EGRESS WINDOW REQUIREMENTS |
| ARE MET. |
| |
| 14) PRODUCT APPROVALS |
| THE PROPOSED PRODUCTS SHALL HAVE STATE- |
| WIDE OR LOCAL PRODUCT APPROVAL IN |
| ACCORDANCE WITH RULE 9B-72 FAC (FOR |
| STATEWIDE PRODUCT APPROVAL SEE |
| WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP): |
| (A) THE SECOND FLOOR ENTRANCE DOORS TO |
| THE RESIDENTIAL UNITS ARE SPECIFIED ON |
| THE DOOR SCHEDULE AS HOLLOW METAL.THIS |
| DOES NOT CORRELATE WITH THE SUBMITTED |
| PRODUCT APPROVAL NOA# 02-0109.03 WHICH |
| IS FOR FIBERGLASS DOORS.AMEND THE DOOR |
| SCHEDULE OR SUBMIT A RELEVANT DOOR |
| PRODUCT APPROVAL. |
| (B) THE SUBMITTED ALUMINUM FRENCH DOOR |
| PRODUCT APPROVAL NOA# 02-0701.12 DOES |
| CORRELATE WITH A STATEWIDE PRODUCT |
| APPROVAL (#FL253) BUT IT IS A POOR COPY |
| AND IS ALSO MISSING DRAWING SHEET |
| 2 OF 4.SUBMIT TWO LEGIBLE COPIES OF A |
| COMPLETE PRODUCT APPROVAL. |
| (C) THE SUBMITTED KAWNEER STOREFRONT |
| DOOR PRODUCT APPROVAL NOA# 02-0523.05 |
| DOES CORRELATE WITH A STATEWIDE PRODUCT |
| APPROVAL (#FL629) BUT IT IS A POOR COPY. |
| SUBMIT TWO LEGIBLE COPIES OF THE PRODUCT |
| APPROVAL. |
| (D) THE SUBMITTED KAWNEER WINDOW WALL |
| PRODUCT APPROVAL NOA# 02-0220.01 DOES |
| CORRELATE WITH A STATEWIDE PRODUCT |
| APPROVAL (FL#627) BUT ONLY ONE COPY WAS |
| SUBMITTED BETWEEN BUILDINGS G & H. |
| SUBMIT NOT LESS THAN TWO COPIES PER |
| BUILDING. |
| (E) THE SUBMITTED PGT INDUSTRIES |
| ALUMINUM SINGLE HUNG WINDOW |
| NOA# 02-0419.13 DOES CORRELATE WITH A |
| STATEWIDE PRODUCT APPROVAL (#FL239) BUT |
| ONLY ONE COPY WAS SUBMITTED BETWEEN |
| BUILDINGS G & H.SUBMIT NOT LESS THAN |
| TWO COPIES PER BUILDING. |
| (F) THE SUBMITTED PGT INDUSTRIES |
| ALUMINUM FIXED WINDOW NOA# 02-0806.04 |
| DOES CORRELATE WITH A STATEWIDE PRODUCT |
| APPROVAL (#FL243) BUT THIS PRODUCT HAS |
| NO IMPACT RATING SO SHUTTERS WILL BE |
| REQUIRED.ALSO ONLY ONE COPY WAS |
| SUBMITTED BETWEEN BUILDINGS G & H. |
| SUBMIT NOT LESS THAN TWO COPIES PER |
| BUILDING AND SUBMIT A CORRESPONDING |
| PRODUCT APPROVAL FOR THE PROPOSED |
| SHUTTERS OR IMPACT RATED FIXED WINDOWS. |
| (G) SUBMIT AT LEAST TWO COPIES OF A |
| PRODUCT APPROVAL FOR IMPACT RATED |
| MULLIONS TO SUIT THOSE WINDOW |
| CONFIGURATIONS WHICH REQUIRE WINDOWS TO |
| BE MULLED TOGETHER. |
| (H) THE SUBMITTED MBCI 5V CRIMP PANEL |
| PRODUCT APPROVAL NOA# 02-0628.02 DOES |
| NOT CORRELATE WITH ANY STATEWIDE PRODUCT |
| APPROVAL.SPECIFY A PRODUCT THAT HAS |
| STATEWIDE OR LOCAL PRODUCT APPROVAL. |
| (I) THE SUBMITTED ELK CORP. VERSASHIELD |
| UNDERLAYMENT PRODUCT APPROVAL |
| NOA# 02-0327.03 DOES NOT CORRELATE WITH |
| ANY STATEWIDE PRODUCT APPROVAL.SPECIFY |
| A PRODUCT THAT HAS A STATEWIDE PRODUCT |
| APPROVAL. |
| |
| 15) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| OLD SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHALL BE INCLUDED WITH THE |
| RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |