2005-03-28 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 TRUSS ENGINEERING SUBMITTAL ON 3/21/05
 AND INDEX SHEET SUBMITTED ON 3/28/05.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) COMMENT ALREADY ADDRESSED BY
 SUBMITTAL OF CALCULATION INDEX SHEETS.
 BUT, WILL NEED NEW INDEX SHEETS WHEN
 ADDRESSING COMMENTS 2 AND 3 BELOW.
  
 2) FBC 1604.1ROOF TRUSS LOADING.THE
 SUBMITTED ROOF TRUSS DESIGN CALCULATIONS
 STATE A BOTTOM CHORD LIVE LOAD OF 10PSF.
 THE REQUIRED MINIMUM BOTTOM CHORD LIVE
 LOAD FOR RESIDENTIAL ATTICS WITH STORAGE
 IS 30 PSF.AMEND THE CALCULATIONS.
  
 3) FBC 1606.1STRESS INCREASE FOR STEEL
 IS NOT ALLOWED.THE WRITERS OF THE
 MITEK SOFTWARE USED FOR DESIGN OF THE
 TRUSSES HAVE ADVISED THAT WHEN THE CODE
 IS STATED AS 'FBC2001/ANSI95' THE
 SOFTWARE USES THE STRESS INCREASE.
 AMEND THE CALCULATIONS TO SHOW
 COMPLIANCE WITH THE PROCEDURE DESCRIBED
 IN THE ATTACHED LETTER FROM MITEK.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS