2005-03-28 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| TRUSS ENGINEERING SUBMITTAL ON 3/21/05 |
| AND INDEX SHEET SUBMITTED ON 3/28/05. |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| 1) COMMENT ALREADY ADDRESSED BY |
| SUBMITTAL OF CALCULATION INDEX SHEETS. |
| BUT, WILL NEED NEW INDEX SHEETS WHEN |
| ADDRESSING COMMENTS 2 AND 3 BELOW. |
| |
| 2) FBC 1604.1ROOF TRUSS LOADING.THE |
| SUBMITTED ROOF TRUSS DESIGN CALCULATIONS |
| STATE A BOTTOM CHORD LIVE LOAD OF 10PSF. |
| THE REQUIRED MINIMUM BOTTOM CHORD LIVE |
| LOAD FOR RESIDENTIAL ATTICS WITH STORAGE |
| IS 30 PSF.AMEND THE CALCULATIONS. |
| |
| 3) FBC 1606.1STRESS INCREASE FOR STEEL |
| IS NOT ALLOWED.THE WRITERS OF THE |
| MITEK SOFTWARE USED FOR DESIGN OF THE |
| TRUSSES HAVE ADVISED THAT WHEN THE CODE |
| IS STATED AS 'FBC2001/ANSI95' THE |
| SOFTWARE USES THE STRESS INCREASE. |
| AMEND THE CALCULATIONS TO SHOW |
| COMPLIANCE WITH THE PROCEDURE DESCRIBED |
| IN THE ATTACHED LETTER FROM MITEK. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| TELEPHONE: (561) 805 6716ROBERT BROWN |