2005-03-23 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| TRUSS ENGINEERING SUBMITTAL ON 3/21/05. |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| 1) 471.025 F.S.THE SUBMITTED TRUSS |
| LAYOUT AND TRUSS DESIGN SHEETS EACH HAVE |
| A STAMPED SIGNATURE OF ALI YEMENICILER, |
| P.E.ALL PLANS/DOCUMENTS PREPARED BY A |
| PROFESSIONAL ENGINEER AND BEING FILED |
| FOR PUBLIC RECORD SHALL BEAR THE |
| ENGINEER'S ORIGINAL SIGNATURE.THE |
| ORIGINAL SIGNATURE OF THE ENGINEER IS |
| REQUIRED ON THE TRUSS LAYOUT AND ON A |
| CALCULATION INDEX SHEET THAT LISTS EACH |
| TRUSS DESIGN SHEET.IF AN INDEX SHEET |
| IS PROVIDED, EACH INDIVIDUAL TRUSS |
| DESIGN SHEET DOES NOT REQUIRE A SEAL AND |
| ORIGINAL SIGNATURE (REF: 61G15-31.003 |
| FLORIDA ADMIN. CODE). |
| |
| 2) FBC 1604.1ROOF TRUSS LOADING.THE |
| SUBMITTED ROOF TRUSS DESIGN CALCULATIONS |
| STATE A BOTTOM CHORD LIVE LOAD OF 10PSF. |
| THE REQUIRED MINIMUM BOTTOM CHORD LIVE |
| LOAD FOR RESIDENTIAL ATTICS WITH STORAGE |
| IS 30 PSF.AMEND THE CALCULATIONS. |
| |
| 3) FBC 1606.1STRESS INCREASE FOR STEEL |
| IS NOT ALLOWED.THE WRITERS OF THE |
| MITEK SOFTWARE USED FOR DESIGN OF THE |
| TRUSSES HAVE ADVISED THAT WHEN THE CODE |
| IS STATED AS 'FBC2001/ANSI95' THE |
| SOFTWARE USES THE STRESS INCREASE. |
| AMEND THE CALCULATIONS TO SHOW |
| COMPLIANCE WITH THE PROCEDURE DESCRIBED |
| IN THE ATTACHED LETTER FROM MITEK. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| TELEPHONE: (561) 805 6716ROBERT BROWN |