Plan Review Notes
Plan Review Notes For Permit 03100433
Permit Number 03100433
Review Stop B
Sequence Number 7
Notes
Date Text
2005-03-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 TRUSS ENGINEERING SUBMITTAL ON 3/21/05.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) 471.025 F.S.THE SUBMITTED TRUSS
 LAYOUT AND TRUSS DESIGN SHEETS EACH HAVE
 A STAMPED SIGNATURE OF ALI YEMENICILER,
 P.E.ALL PLANS/DOCUMENTS PREPARED BY A
 PROFESSIONAL ENGINEER AND BEING FILED
 FOR PUBLIC RECORD SHALL BEAR THE
 ENGINEER'S ORIGINAL SIGNATURE.THE
 ORIGINAL SIGNATURE OF THE ENGINEER IS
 REQUIRED ON THE TRUSS LAYOUT AND ON A
 CALCULATION INDEX SHEET THAT LISTS EACH
 TRUSS DESIGN SHEET.IF AN INDEX SHEET
 IS PROVIDED, EACH INDIVIDUAL TRUSS
 DESIGN SHEET DOES NOT REQUIRE A SEAL AND
 ORIGINAL SIGNATURE (REF: 61G15-31.003
 FLORIDA ADMIN. CODE).
  
 2) FBC 1604.1ROOF TRUSS LOADING.THE
 SUBMITTED ROOF TRUSS DESIGN CALCULATIONS
 STATE A BOTTOM CHORD LIVE LOAD OF 10PSF.
 THE REQUIRED MINIMUM BOTTOM CHORD LIVE
 LOAD FOR RESIDENTIAL ATTICS WITH STORAGE
 IS 30 PSF.AMEND THE CALCULATIONS.
  
 3) FBC 1606.1STRESS INCREASE FOR STEEL
 IS NOT ALLOWED.THE WRITERS OF THE
 MITEK SOFTWARE USED FOR DESIGN OF THE
 TRUSSES HAVE ADVISED THAT WHEN THE CODE
 IS STATED AS 'FBC2001/ANSI95' THE
 SOFTWARE USES THE STRESS INCREASE.
 AMEND THE CALCULATIONS TO SHOW
 COMPLIANCE WITH THE PROCEDURE DESCRIBED
 IN THE ATTACHED LETTER FROM MITEK.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]