2004-09-21 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| REVISION FIRST SUBMITTED 6/30/04 FOR |
| ADDITION TO PERMITTED BUILDING SIZE. |
| AREA WILL BE INCREASED BY 4557 SQ FT |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 7/21/04: |
| |
| 2) IMPACT FEES. THE AREA OF THE BUILDING |
| HAS INCREASED. THE PLANS SHALL BE TAKEN |
| TO PALM BEACH COUNTY BUILDING DEPARTMENT |
| FOR IMPACT FEE ASSESSMENT. THEY SHALL BE |
| STAMPED AT THAT OFFICE AND A COPY OF THE |
| PAID RECEIPT SUBMITTED TO THE CITY OF |
| WEST PALM BEACH DEPT OF CONSTRUCTION |
| SERVICES BEFORE THE REVISION CAN BE |
| PERMITTED. |
| |
| 6) FBC 13-103.0ENERGY CODE COMPLIANCE |
| FORMS.THE STATED CONDITIONED AREAS |
| STILL DO NOT CORRELATE WITH THE AREAS |
| STATED ON THE PLANS. |
| (A) ONE FORM IS STATED TO APPLY TO BOTH |
| UNITS R9 AND R8.THESE UNITS ARE NOT |
| SIMILAR.SHOULD THE FORM BE TITLED |
| 'UNIT R7 AND R8' (WHICH ARE SIMILAR, AT |
| 1,670 SQFT)? |
| (B) IN THAT CASE, SHOULD THE FORM |
| CURRENTLY TITLED R7 ACTUALLY BE R9 |
| (1,817 SQFT)? |
| (C) THE FORM SUBMITTED FOR R10 IS FOR A |
| CONDITIONED AREA OF 1987 SQFT.THIS |
| DOES NOT CORRELATE WITH THE AREA STATED |
| ON THE PLANS, WHICH IS 1,422 SQFT. |
| (D) THE FORM SUBMITTED FOR C5 STATES A |
| "CONDITIONED FLOOR AREA" OF 1,997 SQFT. |
| THE AREA STATED ON THE PLANS IS 960 SQFT |
| (E) THE FORM SUBMITTED FOR C8 STATES A |
| "CONDITIONED FLOOR AREA" OF 1,040 SQFT. |
| THE AREA STATED ON THE PLANS IS |
| 1,770 SQFT. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |