Plan Review Notes
Plan Review Notes For Permit 03100433
Permit Number 03100433
Review Stop B
Sequence Number 5
Notes
Date Text
2004-09-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION FIRST SUBMITTED 6/30/04 FOR
 ADDITION TO PERMITTED BUILDING SIZE.
 AREA WILL BE INCREASED BY 4557 SQ FT
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 7/21/04:
  
 2) IMPACT FEES. THE AREA OF THE BUILDING
 HAS INCREASED. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE THE REVISION CAN BE
 PERMITTED.
  
 6) FBC 13-103.0ENERGY CODE COMPLIANCE
 FORMS.THE STATED CONDITIONED AREAS
 STILL DO NOT CORRELATE WITH THE AREAS
 STATED ON THE PLANS.
 (A) ONE FORM IS STATED TO APPLY TO BOTH
 UNITS R9 AND R8.THESE UNITS ARE NOT
 SIMILAR.SHOULD THE FORM BE TITLED
 'UNIT R7 AND R8' (WHICH ARE SIMILAR, AT
 1,670 SQFT)?
 (B) IN THAT CASE, SHOULD THE FORM
 CURRENTLY TITLED R7 ACTUALLY BE R9
 (1,817 SQFT)?
 (C) THE FORM SUBMITTED FOR R10 IS FOR A
 CONDITIONED AREA OF 1987 SQFT.THIS
 DOES NOT CORRELATE WITH THE AREA STATED
 ON THE PLANS, WHICH IS 1,422 SQFT.
 (D) THE FORM SUBMITTED FOR C5 STATES A
 "CONDITIONED FLOOR AREA" OF 1,997 SQFT.
 THE AREA STATED ON THE PLANS IS 960 SQFT
 (E) THE FORM SUBMITTED FOR C8 STATES A
 "CONDITIONED FLOOR AREA" OF 1,040 SQFT.
 THE AREA STATED ON THE PLANS IS
 1,770 SQFT.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]