Plan Review Notes
Plan Review Notes For Permit 03100433
Permit Number 03100433
Review Stop E
Sequence Number 4
Notes
Date Text
2004-07-13 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE HAVE PLANS SIGNED BY
 ENGINEER WITH FULL LEGAL SIGNATURE AS
 SHOWN ON ORIGINAL PLANS FILE WITH ORIG-
 -INAL PLANS AND PERMIT.
 FS 471.025
  
 2)NOTE: PLEASE CORRELATE RISER AND UNITS
 SHOWN ON PLANS ALONG WITH LOAD CALCULAT-
 -IONS.PLEASE ALSO CORRELATE WITH PANEL
 SCHEDULES.
 SOME UNITS DO NOT MATCH.
  
 3)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPTS ALONG 2' OF WALL SPACE.
  
 4)NOTE: PLEASE SEE FBC 104.6.5 FOR
 INCREASE OF VALUE FOR PERMIT. PLEASE SEE
 BUILDING PLAN REVIEW COMMENTS FOR THIS.
 DUE TO INCREASE OF AREA OF BLDG TO
 INCLUDE ALL TRADES.
  
 5)NOTE: PLEASE SEE POSSIBLE MISPRINT IN
 LOAD CALCS FOR "DETAIL UNITS". SHOULD
 READ RETAIL UNITS. THIS IS ONLY A NOTE.
  
 6 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 NOTED ON PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE SET
 -S FOR REVIEW AND STAMPING.
 PLEASE SEE ONE SET HAS SOME ITEMS
 REDLINED FOR AREAS OF ABOVE COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717