2004-07-13 00:00:00 | ************* UNSAT ***************** |
| |
| 1)NOTE: PLEASE HAVE PLANS SIGNED BY |
| ENGINEER WITH FULL LEGAL SIGNATURE AS |
| SHOWN ON ORIGINAL PLANS FILE WITH ORIG- |
| -INAL PLANS AND PERMIT. |
| FS 471.025 |
| |
| 2)NOTE: PLEASE CORRELATE RISER AND UNITS |
| SHOWN ON PLANS ALONG WITH LOAD CALCULAT- |
| -IONS.PLEASE ALSO CORRELATE WITH PANEL |
| SCHEDULES. |
| SOME UNITS DO NOT MATCH. |
| |
| 3)NOTE: PLEASE SEE 210.52 FOR MISSING |
| RECEPTS ALONG 2' OF WALL SPACE. |
| |
| 4)NOTE: PLEASE SEE FBC 104.6.5 FOR |
| INCREASE OF VALUE FOR PERMIT. PLEASE SEE |
| BUILDING PLAN REVIEW COMMENTS FOR THIS. |
| DUE TO INCREASE OF AREA OF BLDG TO |
| INCLUDE ALL TRADES. |
| |
| 5)NOTE: PLEASE SEE POSSIBLE MISPRINT IN |
| LOAD CALCS FOR "DETAIL UNITS". SHOULD |
| READ RETAIL UNITS. THIS IS ONLY A NOTE. |
| |
| 6 )NOTE: PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| NOTED ON PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW SHEETS INTO COMPLETE SET |
| -S FOR REVIEW AND STAMPING. |
| PLEASE SEE ONE SET HAS SOME ITEMS |
| REDLINED FOR AREAS OF ABOVE COMMENTS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |