2004-07-21 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| REVISION SUBMITTED 6/30/04 FOR ADDITION |
| TO PERMITTED BUILDING SIZE.AREA WILL |
| BE INCREASED BY 4557 SQ FT |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) PERMIT FEES.THE PERMIT AND RADON |
| FEES HAVE BEEN REVISED TO REFLECT THE |
| INCREASED AREA/VALUATION.THE BALANCE |
| OUTSTANDING IS $3349.26 |
| |
| 2) IMPACT FEES. THE AREA OF THE BUILDING |
| HAS INCREASED.THE PLANS SHALL BE TAKEN |
| TO PALM BEACH COUNTY BUILDING DEPARTMENT |
| FOR IMPACT FEE ASSESSMENT. THEY SHALL BE |
| STAMPED AT THAT OFFICE AND A COPY OF THE |
| PAID RECEIPT SUBMITTED TO THE CITY OF |
| WEST PALM BEACH DEPT OF CONSTRUCTION |
| SERVICES BEFORE A PERMIT CAN BE ISSUED. |
| |
| 3) THE PROPOSED BUILDING STRUCTURE NOW |
| TRANSGRESSES LEGAL BOUNDARY LINES |
| BETWEEN THE LOTS WHICH COMBINE TO FORM |
| 'THE SITE'.SUBMIT A COPY OF THE 'UNITY |
| OF TITLE' DOCUMENT SO THAT FBC TABLE 600 |
| BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| NOT APPLICABLE. |
| |
| 4) FBC* 104.2.4SITE SURVEY.THE SITE |
| BOUNDARY HAS CHANGED. A REVISED SIGNED |
| AND SEALED SURVEY DRAWING PREPARED BY A |
| LICENSED SURVEYOR/MAPPER IS REQUIRED. |
| (REF: 472.025(1) FL. STATUTES) |
| |
| 5) ON ONE SET OF PLANS, THE RETAIL AND |
| RESIDENTIAL UNIT REFERENCES HAVE BEEN |
| STRUCK OUT ON STRUCTURAL PLAN SHEETS |
| S1.0, S2.0 AND S3.0 BECAUSE THEY DO NOT |
| CORRELATE TO THE REFERENCES ON THE |
| ARCHITECTURAL PLANS.AMEND THE OTHER |
| TWO SETS TO SUIT. |
| |
| 6) FBC 13-103.0EACH COPY OF THE |
| SUBMITTED ENERGY CODE COMPLIANCE FORMS |
| SHALL HAVE THE CORRECT PERMIT NUMBER |
| (03100433), PROJECT ADDRESS |
| (1930 S DIXIE HWY), AND BUILDER NAME |
| ENTERED IN THE ALLOCATED SPACES.ALSO, |
| THE STATED UNIT REFERENCES (R6, R7 ETC) |
| DO NOT CORRELATE CORRECTLY WITH THE |
| 'CONDITIONED AREAS' STATED ON THE CODE |
| COMPLIANCE FORMS.SUBMIT COMPLETE AND |
| CORRECT FORMS. |
| |
| 7) FBC 13-101.1.6SHELL RETAIL UNITS. |
| THE WHOLE BUILDING (INCL. FUTURE TENANT |
| SPACE) SHALL BE CONSIDERED. SHELL RETAIL |
| UNITS SHALL BE SHOWN TO COMPLY WITH |
| METHOD B (SEE SUB-CHAPTER 4).ALL |
| ASSUMPTIONS MADE ABOUT SYSTEMS, NOT |
| SHOWN ON THE CURRENT PLANS, SHALL BE |
| LISTED AND APPENDED TO THE FORM 400B FOR |
| SUBMITTAL.THIS WILL BE COMPARED, AT A |
| LATER DATE, TO THE ACTUAL SYSTEMS |
| PROPOSED BY THE FUTURE TENANT(S).THE |
| ASSUMPTIONS LISTED ON THE APPENDIX SHEET |
| SHALL BE AT LEAST THE MINIMUM STANDARD |
| (LIGHTING, HVAC ETC) TO ALLOW THE WHOLE |
| BUILDING TO BE OCCUPIED FOR IT'S |
| INTENDED PURPOSE.SUBMIT CODE |
| COMPLIANCE FORMS FOR THE RETAIL UNITS. |
| |
| 8) FBC 13-103.1.2BEFORE A BUILDING |
| PERMIT CAN BE ISSUED, THE SUBMITTED |
| ENERGY CODE COMPLIANCE FORMS SHALL BE |
| SIGNED BY THE BUILDING OWNER, THE |
| OWNER'S ARCHITECT OR OTHER AUTHORIZED |
| AGENT LEGALLY DESIGNATED BY THE OWNER. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| TELEPHONE: (561) 805 6716ROBERT BROWN |
| E-MAIL: [email protected] |