Date Text
2004-07-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ALL ENGINEERED PLANS SHALL BE SIGNED
 WITH FULL SIGNATURE. FAC G1G15-23.002(1)
 (2) & FS 471.025.
 2) SHT P-3 SANT. RISER DIAGRAM, SHOW ALL
 PIPE SIZES AND DRAINAGE FIXTURE UNITS AS
 THEY ACCUMULATE IN THE BLDG. DRAIN. SEC
 104.2.1.
 3) SHT P-4 IF ICE MAKER LINE TO REFRIG.,
 A WATER HAMMER ARRESTOR IS REQUIRED PER
 SECTION 604.9.
 4) SUBMIT A DETAIL FOR TOILET ROOMS IN
 THE RETAIL SPACES. SHOW COMPLIANCE WITH
 SECTION 11-4.15 AND ALL SUBSECTIONS, SEC
 11-4.1.3(10)(A) FOR THOSE WHO HAVE DIFF-
 ICULTY BENDING OR STOOPING, SECTION 11-4
 .16 AND ALL SUBSECTIONS, 11-4.19 AND ALL
 SUBSECTIONS, & 11-4.22 AND ALL SUBSECT-
 IONS.
 5) SUBMIT A FINISH SCHEDULE FOR TOILET
 ROOMS IN THE RETAIL SPACES. SECTION
 104.2.1
  
 REVIEW BY KEN STEVENS