Plan Review Notes For Permit 03100433 |
Permit Number |
03100433 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-01-07 00:00:00 | DENIED: | | RESIDENTIAL: | | 1.PER 2001 FBC(M) 403.3, VENTILATION | | SYSTEMS, FOR OTHER THAN R-3 (ONE & TWO | | FAMILY DWELLINGS), SHALL BE DESIGNED TO | | TO SUPPLY THE MINIMUM OUTSIDE AIR IN | | ACCORDANCE WITH TABLE 403.3.PLEASE | | PROVIDE OUTSIDE AIR CALCULATIONS. | | INDICATE OUTSIED AIR DUCT SIZE, | | MATERIAL, LAYOUT AND INTAKE ON THE PLAN. | | | | 2.PLAN SHEET AC.3 INDICATES DUCT TO | | 2ND FLOOR IN RATED SHAFT. PLEASE PROVIDE | | SHAFT DETAIL. | | | | RETAIL:PLANS ARE CODE COMPLIANT. | | | | PLEASE NOTE: | | PLANS DO NOT INDICATE THE USE OF THE | | RETAIL SPACE.BECAUSE OF THE LOCATION | | AND PROPERTY LINES, ALLOWANCE FOR A | | RESTAURANT MAY BE DIFFICULT SHOULD | | CONSIDERATION NOT BE GIVEN FOR THE | | INSTALLATION OF GREASE DUCT NOT BE MADE | | AT THE BEGINNING OF CONSTRUCTION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|