2004-01-07 00:00:00*********** UNSAT ****************
  
 BLDG "G"
  
 1)NOTE: PLEASE SEE NOTE FOR MAIN AND
 SERVICE ENT CONDUCTORS. PLEASE SEE COND
 ARE RATED FOR 670A'S AND NOTHING TO
 LIMIT LOAD FOR SERVICE. OCP ADDS UP TO
 910A'S. PLEASE SEE 230.42B
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW