2004-01-16 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| **BUILDING G** |
| **NOTE: READ THESE COMMENTS INDIVIDUALLY |
| THEY ARE NOT EXACTLY THE SAME AS THE |
| COMMENTS FOR BUILDING H** |
| |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 11/18/03: |
| |
| 1) THE NOTICE OF COMMENCEMENT SHALL BE |
| RECORDED AT PALM BEACH COUNTY COURTHOUSE |
| AND A COPY SUBMITTED TO THIS OFFICE |
| BEFORE A PERMIT CAN BE ISSUED.BLANK |
| FORMS ARE AVAILABLE FROM THIS OFFICE. |
| |
| 3) 61G1-16.004FL. ADMIN. CODE. SHEETS |
| A.1 TO A.20 HAVE A TITLE BLOCK THE |
| INCLUDES ONLY THE FIRM'S LICENSE NUMBER |
| AA26000691.EACH SHEET SHALL ALSO |
| INCLUDE THE PRINTED ARCHITECT'S LICENSE |
| NUMBER AR0014128.THE MISSING LICENSE |
| NUMBERS MAY BE HANDWRITTEN ON THE PLANS. |
| |
| 5) FBC 13-103.1.2THIS COMMENT HAS NOT |
| BEEN PROPERLY ADDRESSED. THE ONLY ENERGY |
| CODE COMPLIANCE FORM THAT HAS BEEN |
| SIGNED IS THE FIRST/TOP ONE IN EACH |
| PACKAGE (I.E. RESIDENTIAL UNIT 62). NONE |
| OF THE FORMS FOR THE OTHER RESIDENTIAL |
| UNITS HAS BEEN SIGNED BY THE BUILDING |
| OWNER, THE OWNER'S ARCHITECT OR OTHER |
| AUTHORIZED AGENT LEGALLY DESIGNATED BY |
| THE OWNER. |
| |
| 6) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| FBC 13-101.1.6NO ENERGY CODE |
| COMPLIANCE FORMS HAVE BEEN SUBMITTED |
| FOR THE FIRST FLOOR COMMERCIAL UNITS. |
| THE WHOLE BUILDING (INCL. FUTURE TENANT |
| SPACE) SHALL BE CONSIDERED.SHELL |
| BUILDINGS SHALL BE SHOWN TO COMPLY WITH |
| METHOD B (SEE SUB-CHAPTER 4).ALL |
| ASSUMPTIONS MADE ABOUT SYSTEMS, NOT |
| SHOWN ON THE CURRENT PLANS, SHALL BE |
| LISTED AND APPENDED TO THE FORM 400B FOR |
| SUBMITTAL.THIS WILL BE COMPARED, AT A |
| LATER DATE, TO THE ACTUAL SYSTEMS |
| PROPOSED BY THE FUTURE TENANT(S).THE |
| ASSUMPTIONS LISTED ON THE APPENDIX SHEET |
| SHALL BE AT LEAST THE MINIMUM STANDARD |
| (LIGHTING, HVAC ETC) TO ALLOW THE WHOLE |
| BUILDING TO BE OCCUPIED FOR IT'S |
| INTENDED PURPOSE. |
| |
| 11) FBC 1606.2.4SHEET S4.0, WOOD TRUSS |
| CONNECTOR MARK D IS STATED AS HAVING AN |
| UPLIFT CAPACITY OF 1490#.THE SIMPSON |
| HETA 20 WITH 10-10DX1-1/2 NAILS HAS A |
| CAPACITY OF 1240#.AMEND THE PLAN. |
| |
| 12) PRODUCT APPROVALS |
| THE PROPOSED PRODUCTS SHALL HAVE STATE- |
| WIDE OR LOCAL PRODUCT APPROVAL IN |
| ACCORDANCE WITH RULE 9B-72 FAC (FOR |
| STATEWIDE PRODUCT APPROVAL SEE |
| WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP): |
| (A) THE DOOR SCHEDULE, SHEET A.19, |
| STATES THAT DOORS 5, 11 & 18 (SECOND |
| FLOOR ENTRANCE DOORS TO THE RESIDENTIAL |
| UNITS) ARE TO BE IMPACT RATED.THE |
| SUBMITTED MIAMI-DADE PRODUCT APPROVAL |
| NOA# 02-0109.03 WHICH IS FOR NON-RATED |
| FIBERGLASS DOORS.SUBMIT THREE COPIES |
| OF A PRODUCT APPROVAL FOR AN ALTERNATIVE |
| DOOR. |
| NOTE: PRINT AND ATTACH THE RELEVANT |
| STATEWIDE PRODUCT APPROVAL LISTING |
| REFERENCE SHEET FL### (FOR EXAMPLE, SEE |
| SHEET ATTACHED TO EACH OF THE SUBMITTED |
| PRODUCT APPROVALS, DURING PLAN REVIEW, |
| TO EXPEDITE PERMIT ISSUE). |
| |
| 14) FBC* 105.3RESIDENT INSPECTOR. |
| SUBMIT INSPECTOR RESUME' AND LICENSE |
| DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF |
| THE RESIDENT INSPECTOR PROGRAM.A |
| RESIDENT INSPECTOR PROGRAM IS REQUIRED, |
| ON THIS PROJECT, DUE TO THE BUILDING |
| BEING OVER 2 STORIES IN HEIGHT. |
| |
| 15) CONDOMINIUM V APARTMENTS.IF THE |
| DWELLING UNITS ARE TO BE SOLD AS |
| CONDOMINIUMS, NO CERTIFICATE OF |
| OCCUPANCY CAN BE ISSUED UNTIL A |
| 'DECLARATION OF CONDOMINIUM' HAS BEEN |
| SUBMITTED TO THE STATE FOR APPROVAL, AND |
| THEN RECORDED WITH THE CLERK OF THE |
| COUNTY COURT.A RECORDED COPY SHALL BE |
| SUBMITTED TO THE CITY FOR RECORDS, |
| ADDRESSING PURPOSES, AND NOTIFICATION OF |
| PALM BEACH COUNTY PROPERTY APPRAISER'S |
| OFFICE. |
| |
| 16) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| OLD SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHALL BE INCLUDED WITH THE |
| RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |