2005-04-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 STRUCTURAL SUBMITTAL ON 4/14/05 FOR
 PRE-CAST SPECIALTIES, INC. PRE-CAST
 HOLLOWCORE SLAB SHOP DRAWINGS AND
 CALCULATIONS.
  
 1) FBC 1604.1LIVE LOADS.UNDER
 'LOADING DATA', THE SUBMITTED
 CALCULATIONS STATE A LIVE LOAD OF 30 PSF
 WAS INPUT.SHEET 1, NOTE 11 STATES THE
 SAME.THE REQUIRED LIVE LOAD FOR
 DWELLINGS IS 40 PSF (30 PSF IN SLEEPING
 ROOMS ONLY).AMEND THE PLANS AND
 CALCULATIONS TO DEMONSTRATE COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO