Plan Review Notes For Permit 03100433 |
Permit Number |
03100433 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-11-03 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) SHT P.1 PLUMBING NOTES #15, WATTS | | 530C NOT APPROVED FOR MULTI-HEATER USE | | PER MANUFACTURE INFORMATION. WATTS 530 | | APPROVED FOR INDIVIDUAL HEATER USE ONLY. | | PROVIDE INFORMATION FOR THERMAL EXPANS- | | ION CONTROL PER 607.3.2 ALSO SEE WATER | | RISER DIAGRAM SHT P.4 AND WATER HEATER | | DETAIL SHT P.5. | | 2) SHT P.4 WATER HAMMER ARRESTORS ARE | | REQUIRED PER SECTION 604.9 FOR WASH | | MACHINES, DISHWASHERS, AND ICE MAKERS. | | SHOW WATER HAMMER ARRESTORS ON THE WATER | | RISER LOCATED NEAR THE FIXTURES IN AN | | "EFFECTIVE RANGE" NOT IN THE CEILING. | | 3) AN RPZ BACKFLOW IS REQUIRED ON THE | | WATER SERVICE. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|