2003-11-03 00:00:00DENIED: BUILDING G
 1. OUTSIDE AIR REQUIRED AS PER 2001 FBC
 (M) TABLE 403.3.
  
 2. CEILING FIRE DAMPERS REQUIRED AS
 DICTATED BY BUILDING CONSTRUCTION, SEE
 1 HR RATED ASSEMBLY ON PLAN SHEET A.11.
 SEE ALSO DETAIL 15 ON PLAN SHEET A.15.
 PLEASE INDICATE LOCATION OF DAMPERS AS
 REQUIRED PER 2001 FBC(M) 607.6.
  
 3. ATTIC ACCESS OPENING SHALL BE NO LESS
 THAN 30" X 22" AS PER 2001 FBC(M) 306.3
  
 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 -
 1. THE SERVICE PANEL OF THE EQUIPMENT IS
 LOCATED WITHIN 6 FT OF AN ATTIC
 ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE
 OWNER OR SHUT DOWN WHEN THE
 CONDENSATE DRAIN IS NOT WORKING
 PROPERLY.
 4. A NOTICE IS POSTED ON THE ELECTRIC
 SERVICE PANEL INDICATING TO THE
 HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC.
  
 4. PLAN SHEET AC.2 INDICATES TOILET
 EXHAUST AS 4" DRYER DUCT. PLEASE CLARIFY
  
 5. PLEASE CLARIFY IF THE "DUCT SHAFTS"
 HAVE A FIRE RATING. REFERENCE PLAN
 SHEET A.11, FLOOR/CEILING ASSEMBLY.
  
 RETAIL:
 1. FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE AS PER
 2001 FBC(M) 606.2.1 & NFPA 90A 4-4.4.3.
  
 2. PLANS DO NOT INDICATE USE OF THE
 RETAIL SPACE.BECAUSE OF THE LOCATION
 AND PROPERTY LINES, ALLOWANCE FOR A
 RESTAURANT MAY BE DIFFICULT SHOULD
 CONSIDERATION NOT BE GIVEN FOR THE
 INSTALLATION OF GREASE DUCT NOT BE MADE
 AT THE BEGINNING OF CONSTRUCTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.