Plan Review Notes For Permit 03100433 |
Permit Number |
03100433 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-31 00:00:00 | 1) NO FIRE SPRINKLER PLANS PROVIDED | | WITH DRAWINGS. BUILDINGS ARE REQUIRED | | TO BE FIRE SPRINKLER PROTECTED PER | | FS 553.895(2). | | | | 2) PLANS DO NOT DISPLAY ANY FIRE ALARM | | EQUIPMENT. THE REQUIRED FIRE SPRINKLER | | SYSTEM IS REQUIRED TO BE MONITORED. | | | | 3) PLEASE INDICATE PRESCRIPTIVE FOR | | HANDRAILS. | | | | 4) BUILDING ADDRESS REQUIRED ON PROPER | | ELEVATION. | | | | 5) UNIT ENTRY DOORS ARE TO BE AT LEAST | | 20 MINUTE FIRE RATED. | | | | 6) PLEASE INDICATE ON PLANS THE SINGLE | | EXIT DESIGN WITHIN THE UNITS. | | | | 7) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | | 8) NO EMERGENCY LIGHTS SHOWN FOR | | EXTERIOR STAIRS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|