Plan Review Notes
Plan Review Notes For Permit 03100433
Permit Number 03100433
Review Stop E
Sequence Number 1
Notes
Date Text
2003-11-03 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SEE THAT WE ARE NOW UNDER
 THE 2002 NEC. PLEASE ADJUST PLANS.
  
 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 AND COMMENTS FROM OTHER REVIEWERS THAT
 MAY HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 3)NOTE: PLEASE SEE 210.62 FOR "SHOW "
 WINDOW RECEPTS REQ'D.
  
 4)NOTE: PLEASE SEE 2002 NEC FOR CHANGES
 IN ARC FAULT PROTECTION. PLEASE ADJUST.
  
 5)NOTE: PLEASE SEE 240.4C. DEVICES
 RATED OVER 800A'S. SEC'S CONDUCTORS
 MUST MEEET OR EXCEED RATING OF MAIN.
 CONDUCTORS SHOWN ARE RATED FOR A TOTAL
 OF 930A'S.310.16
  
 6)NOTE: PLEASE SIZE GEC TO FOOTER STEEL
 PER 250.66. PER 250.50
  
 7)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF LTS, SEEE FIRE REVIEW COMMENTS.
  
 8)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3, 230.42 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]