Plan Review Notes
Plan Review Notes For Permit 03100433
Permit Number 03100433
Review Stop B
Sequence Number 1
Notes
Date Text
2003-11-18 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) 61G1-16.004(6) FACTHE TITLE BLOCK
 ON THE ARCHITECTURAL PLANS SHALL INCLUDE
 THE PRINTED NAME OF THE ARCHITECT
 SEALING THE DOCUMENT.
  
 4) FBC* 104.2.4SITE SURVEY.A SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED (REF:
 472.025(1) FL. STATUTES)
  
 5) FBC 13-103.1.2THE SUBMITTED ENERGY
 CODE COMPLIANCE FORMS FOR THE
 RESIDENTIAL UNITS SHALL BE SIGNED BY THE
 BUILDING OWNER, OWNER'S ARCHITECT OR
 OTHER AUTHORIZED AGENT LEGALLY
 DESIGNATED BY THE OWNER.
  
 6) FBC 13-101.1.6NO ENERGY CODE
 COMPLIANCE FORMS HAVE BEEN SUBMITTED
 FOR THE FIRST FLOOR COMMERCIAL UNITS.
 THE WHOLE BUILDING (INCL. FUTURE TENANT
 SPACE) SHALL BE CONSIDERED.SHELL
 BUILDINGS SHALL BE SHOWN TO COMPLY WITH
 METHOD B (SEE SUB-CHAPTER 4).ALL
 ASSUMPTIONS MADE ABOUT SYSTEMS, NOT
 SHOWN ON THE CURRENT PLANS, SHALL BE
 LISTED AND APPENDED TO THE FORM 400B FOR
 SUBMITTAL.THIS WILL BE COMPARED TO THE
 ACTUAL SYSTEMS PROPOSED, AT A LATER, FOR
 INSTALLATION BY THE TENANT(S).THE
 ASSUMPTIONS LISTED ON THE APPENDIX SHEET
 SHALL BE AT LEAST THE MINIMUM STANDARD
 (LIGHTING, HVAC ETC) TO ALLOW THE WHOLE
 BUILDING TO BE OCCUPIED FOR IT'S
 INTENDED PURPOSE.
  
 7) FBC* F102.2.4ROOF COVERING IN THE
 FIRE DISTRICT.ANNOTATE THE PLANS TO
 SPECIFY FIRE BARRIER BOARD AND AN
 APPROPRIATE UNDERLAYMENT TO ACHIEVE THE
 REQUIRED CLASS A OR B RATING.
  
 8) FBC* F102.2.7ARCHITECTURAL TRIM ON
 BUILDINGS IN THE FIRE DISTRICT SHALL BE
 CONSTRUCTED OF APPROVED NON-COMBUSTIBLE
 MATERIALS OR FIRE RETARDANT TREATED
 WOOD.THE ELEVATIONS SHOW P.T. CEDAR
 WOOD SHAKE SIDING AND FASCIA, DECORATIVE
 WOOD TRELLIS MEMBERS AND OUTRIGGERS, AND
 WOOD BEAMS.AMEND THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 9) FBC*F102.2.8THE CANVAS AWNING
 SUPPORTS SHALL BE OF NON-COMBUSTIBLE
 MATERIALS AND THE COVERING SHALL BE
 FLAME RESISTANT AS DETERMINED IN
 ACCORDANCE WITH FBC 3103.1.AMEND THE
 PLANS TO DEMONSTRATE COMPLIANCE.
  
 10) FBC 1604.1SHEET S0.2,
 PRE-ENGINEERED WOOD TRUSSES NOTE 4.THE
 TRUSSES SHALL BE DESIGNED FOR A BOTTOM
 CHORD LIVE LOAD NOT LESS THAN 10 PSF
 (RESIDENTIAL ATTICS WITHOUT STORAGE).
 ANNOTATE THE PLANS TO COMPLY.
  
 11) FBC 1606.2.4SHEET S4.0, WOOD TRUSS
 CONNECTION MARK B AND C (DOUBLE ANCHORS)
 ARE STATED AS HAVING TWICE THE UPLIFT
 CAPACITY OF A SINGLE ANCHOR.THIS IS
 NOT CORRECT FOR EMBEDDED ANCHORS SUCH
 HETA & HHETA BECAUSE THE FAILURE MODE IS
 INFLUENCED BY OVERLAPPING OF THE
 CONCRETE 'PULL-OUT CONES' FOR THE TWO
 ANCHORS (SEE 2003 SIMPSON CATALOGUE).
 AMEND THE SCHEDULE.
  
 12) PRODUCT APPROVALS
 THE PROPOSED PRODUCTS SHALL HAVE STATE-
 WIDE OR LOCAL PRODUCT APPROVAL IN
 ACCORDANCE WITH RULE 9B-72 FAC (FOR
 STATEWIDE PRODUCT APPROVAL SEE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP):
 (A) THE SECOND FLOOR ENTRANCE DOORS TO
 THE RESIDENTIAL UNITS ARE SPECIFIED ON
 THE DOOR SCHEDULE AS HOLLOW METAL.THIS
 DOES NOT CORRELATE WITH THE SUBMITTED
 PRODUCT APPROVAL NOA# 02-0109.03 WHICH
 IS FOR FIBERGLASS DOORS.AMEND THE DOOR
 SCHEDULE OR SUBMIT A RELEVANT DOOR
 PRODUCT APPROVAL.
 (B) THE SUBMITTED ALUMINUM FRENCH DOOR
 PRODUCT APPROVAL NOA# 02-0701.12 DOES
 CORRELATE WITH A STATEWIDE PRODUCT
 APPROVAL (#FL253) BUT IT IS A POOR COPY
 AND IS ALSO MISSING DRAWING SHEET
 2 OF 4.SUBMIT TWO LEGIBLE COPIES OF A
 COMPLETE PRODUCT APPROVAL.
 (C) THE SUBMITTED KAWNEER STOREFRONT
 DOOR PRODUCT APPROVAL NOA# 02-0523.05
 DOES CORRELATE WITH A STATEWIDE PRODUCT
 APPROVAL (#FL629) BUT IT IS A POOR COPY.
 SUBMIT TWO LEGIBLE COPIES OF THE PRODUCT
 APPROVAL.
 (D) THE SUBMITTED KAWNEER WINDOW WALL
 PRODUCT APPROVAL NOA# 02-0220.01 DOES
 CORRELATE WITH A STATEWIDE PRODUCT
 APPROVAL (FL#627) BUT ONLY ONE COPY WAS
 SUBMITTED BETWEEN BUILDINGS G & H.
 SUBMIT NOT LESS THAN TWO COPIES PER
 BUILDING.
 (E) THE SUBMITTED PGT INDUSTRIES
 ALUMINUM SINGLE HUNG WINDOW
 NOA# 02-0419.13 DOES CORRELATE WITH A
 STATEWIDE PRODUCT APPROVAL (#FL239) BUT
 ONLY ONE COPY WAS SUBMITTED BETWEEN
 BUILDINGS G & H.SUBMIT NOT LESS THAN
 TWO COPIES PER BUILDING.
 (F) THE SUBMITTED PGT INDUSTRIES
 ALUMINUM FIXED WINDOW NOA# 02-0806.04
 DOES CORRELATE WITH A STATEWIDE PRODUCT
 APPROVAL (#FL243) BUT THIS PRODUCT HAS
 NO IMPACT RATING SO SHUTTERS WILL BE
 REQUIRED.ALSO ONLY ONE COPY WAS
 SUBMITTED BETWEEN BUILDINGS G & H.
 SUBMIT NOT LESS THAN TWO COPIES PER
 BUILDING AND SUBMIT A CORRESPONDING
 PRODUCT APPROVAL FOR THE PROPOSED
 SHUTTERS OR IMPACT RATED FIXED WINDOWS.
 (G) SUBMIT AT LEAST TWO COPIES OF A
 PRODUCT APPROVAL FOR IMPACT RATED
 MULLIONS TO SUIT THOSE WINDOW
 CONFIGURATIONS WHICH REQUIRE WINDOWS TO
 BE MULLED TOGETHER.
 (H) THE SUBMITTED MBCI 5V CRIMP PANEL
 PRODUCT APPROVAL NOA# 02-0628.02 DOES
 NOT CORRELATE WITH ANY STATEWIDE PRODUCT
 APPROVAL.SPECIFY A PRODUCT THAT HAS
 STATEWIDE OR LOCAL PRODUCT APPROVAL.
 (I) THE SUBMITTED ELK CORP. VERSASHIELD
 UNDERLAYMENT PRODUCT APPROVAL
 NOA# 02-0327.03 DOES NOT CORRELATE WITH
 ANY STATEWIDE PRODUCT APPROVAL.SPECIFY
 A PRODUCT THAT HAS A STATEWIDE PRODUCT
 APPROVAL.
 (J) NOTE:
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE TO IDENTIFY WHICH
 PRODUCT OPTIONS/MATERIALS/SIZES ARE TO
 BE USED.
 (K) NOTE:
 STATEWIDE PRODUCT APPROVAL STATUS CAN
 BE CHECKED AT THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 13) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]