Plan Review Notes
Plan Review Notes For Permit 03100367
Permit Number 03100367
Review Stop P
Sequence Number 2
Notes
Date Text
2003-12-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLA. ADMIN. CODE
 FLA. STATUES
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. WASH MACHINE SHALL
 NOT DRAIN THROUGH THE WET VENT FOR THE
 BATHROOM GROUP. 909.1 - CONNECT THE W/M
 DISCHARGE LINE IN DOWNSTREAM OF THE
 BATHROOM FIXTURES. CONNECT THE WATER
 CLOSET LINE INTO THE VENT FOR THE LAV.
 2) SIGNATURE REQUIRED ON SEAL OF ENGIN-
 EER PER FAC 61G15-23.002(1) & FS 471.025
 INITIALS ARE NOT ACCEPTABLE PER FBPE &
 BLDG. OFFICIAL.
  