2003-10-30 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)PROVIDE AREA CALCULATIONS ON THE |
| PLAN; EXISTING AND NEW TOTAL.ADDITIONS |
| OF OVER 25% MUST COMPLY WITH FBC3407.1.2 |
| 2003 AMENDMENT.NOTE ON PLAN (GFCI, |
| SMOKE DETECTORS). |
| |
| 2.)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY.THE PLANS MUST BE |
| STAMPED AND THE RECEIPT ATTACHED TO THE |
| APPLICATION. |
| |
| 3.)ENERGY CALCS SIGNED BY BOTH THE |
| PREPARER AND OWNER/AGENT REQUIRED |
| FBC13-103.1.2. |
| |
| 4.)PE LICENSE NUMBER REQUIRED ON EACH |
| SHEET, FAC61G15-23.002. |
| |
| 5.)CONFIRM THAT THE ADDITION DOES NOT |
| BLOCK THE ONLY EGRESS THAT COMPLIES |
| WITH FBC1005.4 FOR THE EXISTING BEDROOM. |
| |
| 6.)SHEET 3, MTS12, A WOOD TO WOOD |
| CONNECTOR IS SPECIFIED IN A WOOD TO |
| MASONRY APPLICATION.ADDRESS. |
| |
| 7.)TYPICAL WALL SECTION, SHEET 3, |
| BOTTOM OF THE FOUNDATION IS REQUIRED |
| TO BE A MINIMUM OF 12" BELOW GRADE, |
| FBC1804.1.3. |
| |
| 8.)CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC1804.1.7, FLOOR ELEVATION |
| SHALL BE A MINIMUM OF 4" ABOVE FINISHED |
| GRADE, REVISE WALL SECTION. |
| |
| 9.)A ROOF TILE NOA WAS SUBMITTED, |
| CLARIFY. |
| |
| 10.) EFFECTIVE OCTOBER 1, 2003, EITHER A |
| STATEWIDE OR LOCAL PRODUCT APPROVAL IS |
| REQUIRED.FOR MORE INFORMATION, SEE |
| WWW.DCA.STATE.FL.US/FHCD/FBC/COMMITTEES/ |
| PRODUCT_APPROVAL/1_PRODUCT_APPROVAL.HTM |
| |
| PRODUCT APPROVAL WILL BE REQUIRED FOR |
| THE SLIDING GLASS DOOR AND IMPACT |
| PROTECTION FOR THE DOOR AS WELL AS THE |
| MODIFIED BITUMEN AND SINGLE HUNG WINDOW. |
| |
| 11.) ADDITIONAL FEES DUE, $3.90, SEE |
| ATTACHED BZ231392. |