Plan Review Notes For Permit 03100308
Permit Number 03100308
Review Stop P
Sequence Number 1
Notes
Date Text
2003-10-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 1) SHT D1 INDICATES THAT A SINK IS LOCA-
 TED WHERE THE NEW SINK WILL BE INSTALLED
 PLEASE CLAIRFY. 104.2.1
 2) SUBMIT MANUF. SPECIFICATIONS FOR PUMP
 SYSTEM. PUMP SHALL BE LABLED AND LISTED.
 3) A GATE VALVE LOCATED ON THE DISCHARGE
 SIDE OF THE CHECK VALVE SHALL BE INSTAL-
 LED IN THE PUMP OR EJECTOR DISCHARGE
 PIPING BETWEEN THE PUMP OR EJECTOR AND
 THE GRAVITY DRAINAGE SYSTEM.
 4) THE PUMP SYSTEM SHALL TIE INTO A VENT
 LINE. AAV'S ARE NOT DESIGNED FOR POSIT-
 IVE PRESSURE. 916.5.1 & 917.2
 5) SEAL FOR ARCHITECT NOT APPROVED. ALSO
 MORE INFORMATION REQUIRED FOR TITLE
 BLOCK. SEE ATTACHED SHEET. 61G1-16.002
 AND 61G1-16.004
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692