Plan Review Notes For Permit 03100308 |
Permit Number |
03100308 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-11-04 00:00:00 | DENIED: | | 1.SEE COMMENTS BY BUILDING & ELECTRIC, | | TITLE BLOCK REQUIRED AS PER FAC 61G1-16. | | 004. | | | | 2.PLAN SHEET M-1 AHU MOUNTING DETAIL, | | PAN W/FLOAT SWITCH OR AUXILIARY DRAIN | | LINE.PLEASE INDICATE TERMINATION POINT | | OF THE AUXILIARY DRAIN LINE ( AT A | | CONSPICUOUS POINT). | | | | 3.DUCT SMOKE DETECTORS ARE NOT | | IDENTIFIED ON THE PLAN.PLEASE INDICATE | | LOCATIONS OF DUCT SMOKE DETECTORS. SHOW | | COMPLIANCE WITH 2001 606.2.1. | | | | 4. FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | IN NORMALLY OCCUPIED AREAS AS PER NFPA | | 90A 4-4.4.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|