2003-12-19 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-REVISE DESIGN PRESSURES SPECIFIED FOR |
| DOORS AND WINDOWS. SEE TABLES 1606.2B |
| AND 1606.2E FBC 2001 OR PROVIDE CALCS |
| FOR VALUES LOWER THAN THOSE SHOWN ON |
| FBC TABLES.SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| **ALSO, DESIGN PRESSURES SHOWN ON DESIGN |
| PRESSURES FOR OPENINGS CHART SUBMITTED |
| WITH PRODUCT APPROVALS DON'T MATCH |
| THOSE SHOWN ON PLANS. |
| 2-SPECIFY SAFETY GLASS FOR WINDOW AT |
| MASTER BATH SHOWER. SEC. 2405.2 FBC. |
| 3-PROVIDE COMPLETE INFORMATION FOR STORM |
| SHUTTERS UNDER A SEPARATE PERMIT. |
| 4-REVISE TRUSS ANCHOR SCHEDULE AND ALL |
| DETAILS THAT ARE AFFECTED BY SECTION |
| 1609.4.3 FBC 2001 WHICH DOESN'T ALLOW |
| THE STEEL STRESS TO BE INCREASED. |
| PROVIDE ENGINEERING CALCS FOR VALUES |
| OTHER THAN THOSE PUBLISHED ON REVISED |
| CATALOGUE ACCORDING TO THE NUMBER AND |
| TYPE OF NAILS USED.SECTION 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 5-ROOF SHEATHING NOTE ON SHEET A3: |
| A)REVISE MIN. ROOF SHEATHING THICKNESS. |
| NEED 19/32" MIN. THICKNESS. |
| B)ZONE 3 AREAS INCLUDE CORNERS. |
| SEE TABLE 2306.1 CITY AMENDMENTS TO |
| FBC 2001. |
| |
| 6-REVISE SPECIFICATIONS FOR CEILING |
| INSTALLATION AT FRONT & REAR PORCHES. |
| SEE ASTM C-926 FOR MIN. NAIL SIZE |
| REQUIRED.SEC. 2504.2 FBC 2001. |
| 7-ENERGY CALCULATIONS: REVISE UNDER |
| ATTIC AREA. SEE SEC. 604.1.A.1 CHAPTER |
| 13 FBC 2001. |
| 8-SIZE OF FOOTING SHOWN ON TYP. WALL |
| SECTION DOESN'T MATCH SIZE SPECIFIED |
| ON FOUNDATION PLAN. REVISE AS REQ'D. |
| 9-FLORIDA PRODUCT APPROVALS: |
| A)ROOFING REPORT SUBMITTED IS FROM DADE |
| COUNTY. FLORIDA PRODUCT APPROVAL CALLS |
| FOR SBCCI REPORT. RESUBMIT. |
| B)FIXED WINDOWS DADE COUNTY NOAS DON'T |
| MATCH NOAS REFERENCED ON FLORIDA |
| PRODUCT APPROVAL. RESUBMIT. |
| C)MULLIONS DADE COUNTY NOAS SUBMITTED |
| DON'T MATCH THOSE REFERENCED ON THE |
| FLORIDA PRODUCT APPROVAL. RESUBMIT. |
| D)NEED PRODUCT APPROVALS FOR STRUCTURAL |
| CONNECTORS. EG: TRUSS ANCHORS. |
| |
| 10-DESIGNER OF RECORD TO SPECIFY ROOF |
| TILE FASTENERS AS REQUIRED BY SECTION |
| 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |